Input Data (Inverter To Master) - Mitsubishi Electric 700 Series Instruction Manual

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

4.7.3

Input data (inverter to master)

[Master input area (inverter → master)]
Address
(word boundary)
Word
(n: node address)
Bit
0
4(n-1)+0
1
4(n-1)+1
2
4(n-1)+2
3
4(n-1)+3
(1)
Inverter status monitor
Monitors the output signal of the inverter from the network.
Bit
Signal
During
0
forward
Forward rotation: 0
rotation
Forward rotation: 1
During
Forward rotation: 0
1
reverse
Forward rotation: 1
rotation
2
RUN signal Inverter running
Reached the
3
SU signal
frequency
4
— (not used) Always 0
5
OL signal
Overload alarm
Output frequency
6
FU signal
detection
7
ALM signal Fault
8
— (not used) Always 0
Safety alarm
Internal safety circuit
9
signal
fault
10
Edit signal
Edit enabled
0: Command (run command/speed command) can not be given through network
11
NET signal
1: Command (run command/speed command) can be given through network
Output current
12
Y12 signal
detection
Zero current
13
Y13 signal
detection
READY
14
Reset cancel
signal
15
— (not used) Always 0
REMARKS
The values of each bit, "0" and "1," indicate "OFF" and "ON."
(2)
Alarm code
Description of an alarm that occurred in the inverter can be read.
Bit
Name
0 to 7
Alarm code
15
14
13
12
11
10
(3) Life/alarm
Description
Bit0
Bit1
Reverse rotation: 0
Reverse rotation: 0
Reverse rotation: 1
Reverse rotation: 1
When the inverter output frequency reaches or exceeds
Pr.13 Starting frequency, the value changes to "1".
When the output frequency reaches the set frequency, the
value changes to "1".
While stall prevention function is activated, the value
changes to "1".
When the output frequency reaches the frequency set in Pr. 42
(Pr. 43 for reverse rotation), the value changes to "1".
When the inverter protective function is activated to stop
the output (fault), the value changes to "1".
When an internal safety circuit fault (E.SAF, E. 6, E. 7, or
E.CPU) occurs, the value changes to "1".
0: Parameter change disabled (X12 signal = "0")
1: Parameter change enabled (X12 signal = "1")
When the output current is higher than the Pr.150 setting
and persists for longer than the time set in Pr.151, the value
changes to "1".
When the output current is lower than the Pr.152 setting and
persists for longer than the time set in Pr.153, the value
changes to "1".
0: inverter resetting/starting after power is turned on
1: Reset canceling
When an alarm (fault) occurs in the inverter, fault code is displayed. (Refer to page 67)
Applications
9
8
7
6
5
(1) Inverter status monitor
(2) Alarm code
(4) Output frequency monitor
(5) Output current monitor
Operation
During stop
During forward rotation
During reverse rotation
Not used
Description
Cyclic transmission
4
3
2
1
0
Related Parameters
Pr.41
Pr.22, Pr.23, Pr.66
Pr.42, Pr.43
Pr.150, Pr.151
Pr.152, Pr.153
Refer
to
Page
142
144
101
144
192
4
145
145
142
59