Power-Failure Deceleration Stop Function (Pr. 261) - Mitsubishi Electric 700 Series Instruction Manual

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

Operation selection at power failure and instantaneous power failure

5.13.2 Power-failure deceleration stop function (Pr. 261)

When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated and re-
accelerated to the set frequency.
Parameter
Number
Power failure stop
261
selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
Power
ON
Pr. 261 = 1
Power
During deceleration
at occurrence of power failure
During stop
at occurrence
of power failure
STF
REMARKS
When automatic restart after instantaneous power failure is selected (Pr. 57 ≠ "9999"), power failure stop function is invalid and
automatic restart operation after instantaneous power failure is valid.
When the power failure deceleration to stop function is active (Pr.261 = "1"), the inverter will not start by turning the power ON
while the start signal (STR/STF) is being input through FL remote communication. After switching ON the power, turn OFF the
start signal once and then ON again to make a start.
156
Initial
Name
Value
0
OFF
Pr. 261 = 0
Pr. 261 = 1, 2
Time
Time
Power
STF
Setting
Range
Coasts to stop.
0
When undervoltage or power failure occurs, the inverter output
is shut off.
When undervoltage or a power failure occurs, the inverter can
1
be decelerated to a stop.
When undervoltage or a power failure occurs, the inverter can
be decelerated to a stop.
2
If power is restored during a power failure, the inverter
accelerates again.
(1) Parameter setting
When Pr. 261 is set to "1" or "2", the inverter decelerates to a
stop if an undervoltage or power failure occurs.
(2) Operation outline of deceleration to stop at power
failure
When undervoltage or power failure has occurred, the output
frequency is decreased and controlled so that the converter
circuit (DC bus) voltage is constant and decreased to 0Hz to
stop.
(3) Power failure stop function (Pr. 261 = "1")
If power is restored during power failure deceleration,
deceleration to a stop is continued and the inverter remains
stopped. To restart, turn OFF the start signal once, then turn it
ON again.
ON
Not started as inverter
Output frequency
is stopped due to
power failure
OFF
ON
Description
Time