Harmonic Suppression Guideline In Japan - Mitsubishi Electric 700 Series Instruction Manual

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

3.1.4

Harmonic suppression guideline in Japan

Harmonic currents flow from the inverter to a power receiving point via a power transformer. The harmonic suppression
guideline was established to protect other consumers from these outgoing harmonic currents.
The three-phase 200V input specifications 3.7kW or less are previously covered by "Harmonic suppression guideline for
household appliances and general-purpose products" and other models are covered by "Harmonic suppression guideline for
consumers who receive high voltage or special high voltage". However, the transistorized inverter has been excluded from the
target products covered by "Harmonic suppression guideline for household appliances and general-purpose products" in
January 2004 and "Harmonic suppression guideline for household appliances and general-purpose products" was repealed
on September 6, 2004.
All capacity and all models of general-purpose inverter used by specific consumers are covered by "Harmonic suppression
guideline for consumers who receive high voltage or special high voltage" (hereinafter referred to as "Guideline for specific
consumers").
"Guideline for specific consumers"
This guideline sets forth the maximum values of harmonic currents outgoing from a high-voltage or especially high-voltage
consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this
guideline requires that consumer to take certain suppression measures.
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Received Power Voltage
6.6kV
22kV
33kV
(1)
Application for specific consumers
Class
Three-phase bridge
3
(Capacitor smoothing)
Table 3 Equivalent Capacity Limits
Received Power Voltage
6.6kV
22/33 kV
66kV or more
Table 4 Harmonic Contents (Values at the fundamental current of 100%)
Reactor
5th
Not used
65
Used (AC side)
38
Used (DC side)
30
Used (AC, DC sides)
28
5th
7th
11th
3.5
2.5
1.6
1.8
1.3
0.82
1.2
0.86
0.55
Install, add or renew
equipment
Calculation of equivalent
capacity total
Equal to or less
than reference
capacity
Equivalent
capacity total
Above reference
capacity
Calculation of outgoing
harmonic current
Not more than
harmonic current upper
limit?
Equal to or less
than upper limit
Harmonic suppression
measures unnecessary
Table 2 Conversion Factors for FR-E700 Series
Circuit Type
Without reactor
With reactor (AC side)
With reactor (DC side)
With reactors (AC, DC sides)
Reference Capacity
50kVA
300kVA
2000kVA
7th
11th
13th
41
8.5
7.7
14.5
7.4
3.4
13
8.4
5.0
9.1
7.2
4.1
EMC and leakage currents
13th
17th
1.3
1.0
0.69
0.53
0.46
0.35
More than upper limit
Harmonic suppression
measures necessary
17th
19th
23rd
4.3
3.1
2.6
3.2
1.9
1.7
4.7
3.2
3.0
3.2
2.4
1.6
19th
23rd
Over 23rd
0.9
0.76
0.70
0.47
0.39
0.36
0.32
0.26
0.24
Conversion Factor (Ki)
K31= 3.4
K32 = 1.8
K33 = 1.8
K34 = 1.4
25th
1.8
1.3
2.2
1.4
3
35