Terminal Connection Diagram; Wiring - Mitsubishi Electric 700 Series Instruction Manual

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

Wiring

2.1
Wiring
2.1.1

Terminal connection diagram

Sink logic
Main circuit terminal
Control circuit terminal
MCCB
Three-phase
AC power
supply
24V external power supply
24V power supply
Common terminal
Safety stop signal
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common
Node address setting
NOTE
To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
14
*
1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1 and P/+.
Earth
(Ground)
Jumper
MC
P1
R/L1
S/L2
T/L3
Earth
(Ground)
+24
SD
Shorting
wire
S1
Output
shutoff
S2
circuit
PC
FL remote
communication
connector
X1
X10
Brake unit
(Option)
*1
R
*3
PR N/-
*2
P/+
Inrush current
V
limit circuit
W
Main circuit
Control circuit
Y0
SE
24V
D1 D2
D3 D4
*2 A brake transistor is not built-in to the 0.1K
and 0.2K.
*3 Brake resistor (FR-ABR, MRS, MYS type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor cannot be connected
to the 0.1K and 0.2K.)
Motor
IM
Earth (Ground)
Open collector output
Open collector output Y0
(Safety monitor output 2)
Open collector output common
Sink/source common
LED (operation status display)
D1: Communication setting status LED (CHG)
D2: Device status LED (DEV)
D3: Reception/transmission LED (TX/RX)
D4: Remote status LED (RMT)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents