5.20.2 Operation panel frequency setting/key lock operation selection (Pr. 161)

The setting dial of the operation panel can be used for setting like a potentiometer.
The key operation of the operation panel can be disabled.
Parameter
Name
Number
Frequency setting/key lock
161
operation selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
(1)
Using the setting dial like a potentiometer to set the frequency.
Operation example Changing the frequency from 0Hz to 60Hz during operation
Operation
1.
Screen at power-ON
The inverter starts up in the Network operation
mode. The monitor display appears.
2.
Change the X12 signal (Bit11) setting to "1."
X12 signal (Bit11) gives a control input
command through FL remote communication.
3.
Press
to choose the PU operation mode.
4.
Press
to choose the parameter setting
mode.
5.
Turn
until
6.
Press
to read the currently set value.
"
"(initial value) appears.
7.
Turn
to change it to the set value "
8.
Press
to set.
9.
Mode/monitor check
Press
twice to choose the monitor/
frequency monitor.
10.
Press
to start the inverter.
11.
Turn
until "
The flickering frequency is the set frequency.
You need not press
Initial Value
0
(Pr. 161) appears.
".
Flicker Parameter setting complete!!
" appears.
.
Setting from the operation panel
Setting
Description
Range
0
Setting dial frequency setting
1
Setting dial potentiometer
10
Setting dial frequency setting
11
Setting dial potentiometer
Display
PU indicator is lit.
PRM indicator is lit.
(The parameter number read previously
appears.)
The frequency flickers for about 5s.
Key lock invalid
Key lock valid
5
183