Servicing Space Requirements for the Outdoor Units
The outdoor unit requires servicing space to perform periodical maintenance and other tasks. Make
sure that there is sufficient servicing space in accordance with the following diagram.
When anchoring the outdoor unit with anchor bolts, there should be a sufficient space for handling
and tightening the anchor bolts.
GYEQ20AN
[Single unit installation]
500 or more
*1. Provide a maintenance access with a width of 500 mm or more on either side.
*2. In the case of the installation of multiple outdoor units, provide a maintenance
access with a width of 500 mm or more on either side of every installation group of
three outdoor units.
*3. Provide a passage from the doorway of the outdoor unit installation site to the front
of each outdoor unit with a width of 600 mm or more.
*4. If you install 4 (four) or more outdoor units together, please consult us.
*5. At the time of actual installation, decide on the installation space in consideration of
short circuit.
*6. Maintain the isolated distance regulated by a fireproof evaluation label from the
outdoor unit to any flammable materials.
*7. Install the outdoor units at a place that can bear the operation and the weight of the
outdoor units.
GYEQ30AN
[Single unit installation]
500 or more
100 or more
or
500 or more
*1. Provide a maintenance access with a width of 500 mm or more on either side.
*2. In the case of the installation of multiple outdoor units, provide a maintenance
access with a width of 500 mm or more on either side of every installation group of
three outdoor units.
*3. Provide a passage from the doorway of the outdoor unit installation site to the front
of each outdoor unit with a width of 600 mm or more.
*4. If you install 4 (four) or more outdoor units together, please consult us.
*5. At the time of actual installation, decide on the installation space in consideration of
short circuit.
*6. Maintain the isolated distance regulated by a fireproof evaluation label from the
outdoor unit to any flammable materials.
*7. Install the outdoor units at a place that can bear the operation and the weight of the
outdoor units.
33
4 Servicing Space Requirements for the Outdoor Units
[Multiple unit installation]
100 or more
Front
*1
*1
Front
100 or more
or
500 or more
Passage
100 or more
opening
or
500 or more
2290 or more
100 or more
100 or more
*1
Front
*1
Front
Passage
100 or more
opening
or
500 or more
2700 or more
100 or more
5870 or more
1690 100 or more
1690
100 or more
1690
Front
4180 or more
100 or more
1690
100 or more
1690
*1
500
or more
Front
*3
600
or more
Passage
opening
[Multiple unit installation]
7100 or more
100 or more
100 or more
2100
2100
2100
Front
100 or more
5000 or more
100 or more
2100
2100
*1
500
or more
Front
*3
600
or more
Passage
opening
– 5 –
SiAUY361411EA
*2
500 or more
Passage
opening
4180 or more
1690
100 or more
1690
Front
*3
600
or more
Front
*3
600
or more
Passage
opening
022580-02E01
*2
500 or more
Passage
opening
5000 or more
100 or more
2100
2100
Front
*3
600
or more
Front
*3
600
or more
Passage
opening
022581-01E01
0FGHP-EN0801 DGJ002
Device Overview

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gyeq30an

Table of Contents