Daikin GYEQ20AN Service Manual page 231

Gas heat pump air conditioner heat recovery r-410a 50 hz
Table of Contents

Advertisement

SiAUY361411EA
Inspecting and replacing the drain filter (neutralizer, packing, oil
7
absorbing mat)
Part name Neutralizer, packing, oil absorbing mat
Tools/materials Spanner, pliers
Step
(1) See "Basics" (page 213)
(2) Check the drain filter
interior
(3) Refill neutralizer and
wash the filter
(4) Install the oil absorbing
mat
(5) Replace the packing
Maintenance / Service Data
1. Remove the drain filter lid.
2. Remove the oil absorbing mat.
3. Check if there is any neutralizer remaining and the degree of
contamination in the case.
To check the degree of contamination, remove the remaining
neutralizer from the drain filter.
(This is in order to check how much the neutralizer at the bottom of
the drain filter is contaminated.)
1. If there is no neutralizer remaining, refill neutralizer.
2. If the filter is contaminated, wash it with water or replace it.
Install the oil absorbing mat.
Replace the lid packing.
Neutralizer
Task
Lid
Packing
Oil absorbing mat
[Note]
Do not fill with neutralizer here.
Otherwise, the lid will not close.
Maintenance
Remarks
Carefully install the mat in
place.
Carefully install the new
packing so that it is free
from foreign matter and
scratches.
023324-00E
220

Hide quick links: