Configuring the Outdoor Unit DIP Switches (Check)
CAUTION
Be sure to check the DIP switch settings even if it is not necessary to change them from the factory
default settings.
After changing any DIP switch setting or connector, you have to turn the power off and on again for the
new setting to take effect.
When you want to reset the outdoor unit power supply, turn off the power and make sure that none of the
LEDs on the PCB are lit before turning the power on again. An attempt to reset the power supply with a
LED lit may fail due to electricity remaining in the circuit.
Configuring the DIP switches on the main circuit board
Use the following tables to check/configure the DIP switches.
SW
Name
No.
DSW1
Piping length
(equivalent length)
Heating temperature
level
Cooling/heating
selection priority
Fuel gas type
Device Overview
Before accessing the DIP switches, make sure that all of the LEDs on the PCB are
off after the power source is turned off. Attempting to access the DIP switches with
any LED lit can result in an electrical shock due to electricity remaining in the
circuit.
Parameter
Description
1
2
off
off
Piping length is 30 m or less.
on
off
Piping length is between 30 m and 80 m.
off
on
Piping length is between 80 m and 130 m.
on
on
Piping length is 130 m or more.
3
4
Heating temperature level is set to
off
off
"Standard".
on
off
Heating temperature level is set to "Low".
off
on
Heating temperature level is set to "High".
Heating temperature level is set to "Outdoor
on
on
Air Temperature Processing".
on
Priority to the indoor unit (remote controller)
off
Priority to the outdoor unit *
6
7
8
off
off
off
Natural gas
2 How to Perform a Test Run
On-site
Factory
configuration
default
1: off
Required
2: off
Configure
3: off
when
4: off
required.
Configure
when
on
required.
Determined
Confirmation
by factory
default
– 3 –
Test Run Manual
Remarks
Be sure to set the switch on.
only