34
Receiver Temperature Sensor System Failure
Sub-code 0: While the unit is running, receiver temperature 31 is reported as 200°C (which means that
Description
of the failure
Sub-code 1: While the unit is running, receiver temperature 31 is reported as 201°C (which means that
Receiver temperature sensor failure; harness failure; main circuit board failure
Possible
causes
of the failure
Flow chart
Is receiver temperature
sensor normal?
YES
Check whether sensor
connected properly to Main
Circuit Board's Harness.
Troubleshooting
receiver temperature sensor 31 is disconnected).
receiver temperature sensor 31 is shorted).
Inspect intake air
NO
temperature sensor.
Flow Charts for Troubleshooting
028037-00E
Error
JF
code
160