Troubleshooting the Outdoor Unit
displayed
outdoor
111
Indoor Unit system
Code
Run
Inspection
on
indicator Unit No.
lamp
unit
F6
Blinking Blinking Blinking
F7
Blinking Blinking Blinking
F9
Blinking Blinking Blinking
FH
Blinking Blinking Blinking
FJ
Blinking Blinking Blinking
H0
Blinking Blinking Blinking
H1
Blinking Blinking Blinking
H6
Blinking Blinking Blinking
J1
Blinking Blinking Blinking
J2
Blinking Blinking Blinking
J3
Blinking Blinking Blinking
J5
Blinking Blinking Blinking
J6
Blinking Blinking Blinking
J7
Blinking Blinking Blinking
J8
Blinking Blinking Blinking
J9
Blinking Blinking Blinking
JA
On
Off
Blinking
JA
Blinking Blinking Blinking
JH
Blinking Blinking Blinking
JJ
Blinking Blinking Blinking
JF
Blinking Blinking Blinking
L1
Blinking Blinking Blinking
On
L8
On
Off
On
L8
On
Blinking
Off
LE
Blinking Blinking Blinking
LF
Blinking Blinking Blinking
On
Blinking Blinking
Off
On
Blinking Blinking
Off
On
Blinking Blinking
Off
On
Blinking Blinking
Off
P0
Blinking Blinking Blinking
P3
Blinking Blinking Blinking
U2
Blinking Blinking Blinking
U3
Blinking Blinking Blinking
U4
Blinking Blinking Blinking
Blinking Blinking Blinking
Blinking Blinking Blinking
Blinking Blinking
Code
displayed
on
remote
controller
Discharge Temperature Sensor Disconnected /
F6
Shorted
F7
Abnormal Engine Room Temperature
F9
Short of Refrigerant
FH
Compressor Oil Detected Too Low
FJ
Abnormal High-Side Differential Pressure
H0
Misfire Detected
H1
Clutch Failure
H6
Indoor Unit Electronic Expansion Valve Failure
J1
Air-Fuel Ratio Controller Failure
Intake Air Temperature Sensor 1 Disconnected /
J2
Shorted
Outdoor Air Temperature Sensor Disconnected /
J3
Shorted
J5
Outdoor Unit Electronic Expansion Valve Failure
J6
Oil Return Solenoid Valve Failure
J7
High-Side Pressure Sensor System Failure
J8
Exhaust Temperature Sensor Disconnected
J9
Low Pressure Side Sensor Disconnected / Shorted
Compressor Automatic Emergency Run (during
JA
continued running)
JA
Compressor Automatic Emergency Run
JH
Pressure Sensor Failure
JJ
Oil Temperature Sensor Disconnected / Shorted
JF
Receiver Temperature Sensor System Failure
L1
Abnormal Exhaust Temperature
Periodic Inspection Reminder (Note: This is not an
error message)
Off
Off
In the case of 200 or less hours remaining before the
next periodic inspection
Periodic Inspection Reminder (Note: This is not an
L8
error message)
In case the next periodic inspection time has passed
LE
Starter Relay Failure
LF
BS Unit Circuit Switch Failure
M1
Centralized Controller P Board Failure
M8
Transmission Failure between Centralized Controllers
MA
Centralized Controller Mismatch
MC
Centralized Controller Address Incorrect
P0
Too Many Indoor Units Connected
P3
Total Indoor Unit Capacity Too Large
Inter-CPU Communication Failure / Software
U2
Mismatch / ROM Abnormal
U3
Inter-Unit Communication Failure
U4
Outdoor/Indoor Unit Transmission Failure
Transmission Failure between Remote Control and
U5
Indoor Units
U7
External Control Adaptor Failure
Transmission Failure between Master and Slave
Off
U8
Remote Control Units (Slave Remote Control Unit
Failure)
SiAUY361411EA
Error
Troubleshooting