Inspecting the Outdoor Unit
1.6
Inspecting the Regulator
While blowing in air through the gas inlet, check the hole open to the atmosphere for any leaks.
(Submerge the regulator in water and check for any leaks based on whether air bubbles are
seen.)
1.7
Inspecting the Valve Clearance
1. With the bonnet cover removed, set the cylinder being tested to the top of the compression
2. Measure the valve clearance using a thickness gauge.
Standard valve clearance
179
Container
filled with water
stroke.
Measuring points
Valve
clearance
Hole open to
the atmosphere
Valve rocker arm
SiAUY361411EA
air
Gas inlet
Regulator
025947-00E
Set value
0.25 to 0.35 mm
Adjustment screw
Lock nut
010612-01E
Parts Inspection