Operating instructions Indoor unit for air-water-heat pumps Daikin Altherma integrated solar unit Operating instructions English Daikin Altherma integrated solar unit Daikin Altherma EHS(X/H)04P30A EHS(X/H)B04P30A EHS(X/H)08P30A EHS(X/H)B08P30A EHS(X/H)08P50A EHS(X/H)B08P50A EHS(X/H)16P50A EHS(X/H)B16P50A...
Back) installation and operating instructions. Only applicable for the pressurised solar system. – When connecting to a Daikin solar system; the associated installation and operating instructions. Only valid/available if a room regulator is connected – If a Daikin FWXV(15/20)AVEB is connected; the associated Only valid/available if a mixer module is connected installation and operating instructions.
1.4 Intended use 1.5 Instructions for operating safety The Daikin Altherma EHS(X/H) may only be used for preparation ● Work on the Daikin Altherma EHS(X/H) (such as setup, of hot water, as a room heating system, and depending on its servicing, connection and initial start-up) is only to be carried design, as a room cooling system.
(cooling). downstream of the hot water extraction cools the lower area of The storage tank on the Daikin Altherma EHS(X/H) is built in such the integrated storage tank to maximum effect. a way to enable the heat pump system to be combined with a The drinking water is heated indirectly in a corrosion resistant Daikin solar system without needing an additional hot water tank.
2.1.3 Safety management The total security management of the Daikin heat pump system is assumed by the electronic control integrated in the Daikin Al- therma EHS(X/H). In the event of a water shortage, loss of refrig- erant or undefined operating states, a safety switch-off is per- formed.
Product description 2.2.5 Device external and internal design Daikin Altherma EHS(X/H)B...P50A Fig. 2-5 Design and components of the Daikin Altherma EHS(X/H)B...P50A (external view and internal design) For legend descriptions see tab. 2-1 Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit...
Page 11
of polypropylene with PUR hard foam heat Solar - Flow (3/4" IG) Flow temperature sensor backup heat- insulation) (nur Typ Daikin Altherma EHS(X/H)B) Filling and drainage connection or Solar - Return flow (3/4" IG) Solar - Return flow connection...
Blue: Operating mode with expert technician authori- Heater) is used at inflow target temperatures of over sation. 50°C, the efficiency (COP) of the Daikin Altherma EHS(X/H) can be affected negatively (depending on the outside temperature). 3.2 Display and operating elements...
3.4.2). Superfluous elec- Independent of the setting of the rotary switch, the tronic components are switched off. Daikin Altherma EHS(X/H) operates in accordance with the operating mode set in the switch position "Oper- Mixer circuit or which has been activated by a ating Mode"...
– room heating, room cooling and the – sanitary hot water generation. Independent of the setting of the rotary switch, the Daikin Altherma EHS(X/H) operates in accordance with the operating mode set in the "Operating switch position or that has been acti- Mode"...
Keylock Function In this rotary switch position, the rotary switch can be used to call up all the system temperatures, the type of Daikin Altherma EHS(X/H), various software information and the operating sta- tuses of all system components, one after the other. The number of displayed parameters depends on the connected components.
Page 16
Operation Display operating data overview Short Explanation of the displayed value The current operating data for the Daikin Altherma EHS(X/H) are designation shown on the RoCon HP Controller in the "Overview" information TVBH2 = TVBH level. Current heating return flow temperature, sec-...
In this mode, the Daikin Altherma EHS(X/H) is shifted to the stand-by mode. The frost-protection function (see section 3.6.5) remains in place. In order to maintain this function,...
– The frost protection function is not active in any of gramme. the connected heating circuits, and – Daikin Altherma EHS(X/H) has been switched on 3.4.3 Temperature setting Daytime room temperature for at least 5 mins. The set room temperatures for room heating during the day are...
A separate input for each individual day of the week is Begin unscheduled hot water generation. possible, or in blocks of "Monday to Friday", "Saturday to Sunday" and "Monday to Sunday". Daikin Altherma EHS(X/H) Operating instructions Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Page 20
For the time period "Entire week", the end time in the 1st switching cycle changed from 22:00 to 21:30. In all the weekdays the 1st switching cycle is also changed from 22:00 to 21:30. Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
[T-Room 1 Setpoint] applies. Daikin Altherma EHS(X/H), the direct heating circuit, the hot – The hot water generation is not affected. water generation and any optionally connected components in –...
Requirement: A valid terminal address is assigned to the An overview is displayed. RoCon B1 control element of the Daikin Altherma EHS(X/H) or ● Use the rotary switch to select and confirm the [Language], the EHS157034 room station. [Date] or [Time] parameters.
3.5.1 Manual Operation Quite Mode means that the exterior heat pump unit is operating Manual Operation is used to regulate the Daikin Altherma at reduced output. This reduces the operating noise caused by EHS(X/H) manually to a specific flow temperature. The manual the exterior heat pump unit.
– Under floor heating system: 0.5 to 0.9. Access Rights Setup Expert Keylock Function Access Rights Outdoor type Access Rights Access Rights Fig. 3-12 Entering the access code Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
[Cooling Setpoint adj] by a maximum of 5°C up or down. The lower temperature limit is limited by the parameter [Min T-Flow Cooling]. Daikin Altherma EHS(X/H) Operating instructions Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
(see info parameter [T-HS Set- If the inflow heating temperature drops below 7°C, the Daikin Al- point], section 6.10) is determined automatically in accordance therma EHS(X/H) heats up until the temperature reaches at least with the set heating/cooling curve depending on the outside tem- 12°C once more.
3.6.7 Reset to factory settings (Reset) This function serves to prevent bacterial contamination in the hot If the Daikin Altherma EHS(X/H) no longer works properly and water storage tank. For accurate controllers for drinking water hy- any other cause for the malfunction cannot be detected, it may be giene, refer to the national provisions.
Possible setting values for this rotary switch setting can be seen in chapter 6.2.4. 3.6.9 Remote control via Internet Using an optional gateway (EHS157056), the Controller RoCon HP can be connected to the internet. This means that the Daikin Altherma EHS(X/H) can be controlled remotely via mobile phone (using an App).
Commissioning Commissioning 4.2.2 Start-up WARNING! ● A Daikin Altherma EHS(X/H) that is installed or If the storage temperature falls below a certain started incorrectly may not operate properly and is minimum value, the safety settings of the Daikin dangerous for the health and safety of individuals.
● If the heating system is not drained and there is a risk of frost, the power supplies must be secured and the external main switch must remain switched If the Daikin Altherma EHS(X/H) is not required for a long time, it Fig. 5-1 Connecting the drain- Optional: Removing the connec- can be temporarily decommissioned.
● Connect the drainage hose to the combined filling and drainage valve on the Daikin Altherma EHS(X/H). ● Open the combined filling and drainage valve on the Daikin- Altherma EHS(X/H). ● Allow the heating and hot water circuit to drain.
Depending on the version of the device software certain information parameters for the device, not described in tab. 6-2, can be displayed at this level. For this see tab. 6-12. Daikin Altherma EHS(X/H) Operating instructions Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Cooling Setpoint adj Parallel displacement of the cooling characteristic curve to match the set value. -5.0 to +5.0 kW 0.0 K Tab. 6-3 Parameter in rotary switch setting "Configuration" level "HC Configuration" Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
2] with the individual day room temperatures set. The hot water generation takes place according to [DHW Program 2]. Tab. 6-6 Parameter in rotary switch setting "Operating Mode" Daikin Altherma EHS(X/H) Operating instructions Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Target hot water temperature for the 3rd switching cycle of the timer programmes [Automatic 1] 10 - 70°C 48 °C 1 °C and [Automatic 2]. Tab. 6-9 Parameter in rotary switch setting "DHW Set Temp" Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
No selection Activation switches to the local device. Contr BM1/BE1 #X Activation switches to the Daikin Altherma EHS(X/H) with the bus ID X. Mix Valve #X Activation switches to the mixer module with the bus ID X. Tab. 6-11 Parameter in rotary switch setting "Remote Param"...
Display of protocol (error and information messages). Here we display the saved messages of the Daikin Altherma EHS(X/H) and the connected data bus units with date a code, in each case as a menu item. By selecting an entry with the rotary switch, all other corresponding information...
1-20: Causes a correction of the set flow temperature (parallel shift of the heat curve) by the set factor. For example: If the measured temperature is 2 K below the set value, the set flow temperature is raised 2-times the set value. Daikin Altherma EHS(X/H) Operating instructions Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Page 40
Contact your specialist heating technician in this regard: Setting the cooling inflow target temperature (fixed value) when cooling mode is active. Tab. 6-15 Parameter in rotary switch setting "Configuration" level "Mixer Config" Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Operators of Daikin heat pump systems are subject to the fol- vocational training and who have taken part in lowing obligations: advanced training sessions recognised by the appropriate responsible authorities.
7.5). ● Before beginning work on live parts, disconnect 12. Clean plastic surface of Daikin Altherma EHS(X/H) with a all of the systems circuits from the power supply soft cloth and mild cleaning agent. Do not use any...
1). During the filling procedure, water can leak from ● Fill the storage tank on the Daikin Altherma EHS(X/H) until potential leaking sites, which, in the event of contact water comes out of the connection (fig. 7-2, item 23), that with live parts, can result in an electric shock.
Page 44
Unlocking button of the drive KFE cock lock Ball cock Hand lever Water cock Automatic bleeder Valve drive 3UVB1, 3UV DHW 3-way diverter valve Fig. 7-3 Filling the heating circuit Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Displays an active error message (controller fault) 8.1.3 Troubleshooting E 9001/80 Fault T-return Troubleshooting the electrical, coolant and hydraulic systems of the Daikin Altherma EHS(X/H) may be per- Inside Unit: Heating Module Address: formed only by authorised and trained heating experts.
Operating data are not then switch on again. Operating system of control unit crashed. updated ● Have the heating system checked by a Daikin heating technician. Heating request switched off (e.g. switching ● Check the operating mode setting. time program is in the economy phase, exter- ●...
Page 47
Water flow too low. check that there is sufficient water pressure (>0.5 bar), if necessary, refill the heating water. ● Have the heating system checked by a Daikin heating technician. ● Increase parameter [Heat-Slope]. ● Have the heating system checked by a Daikin heating Target value range is too low.
Page 48
Water flow too low. check that there is sufficient water pressure (>0.5 bar), if necessary, refill the heating water. ● Have the heating system checked by a Daikin heating technician. "Cooling" switched off (e.g. room thermostat ● Check the operating mode setting.
If necessary, bleed the water until open. the pressure lies in central permissible range. ● Have the heating system checked by a Daikin heating Safety pressure relief valve is stuck. technician. Tab. 8-1 Possible malfunctions of the Altherma EHS(X/H) 8.3 Fault codes...
As a result, an extra heater (e.g. backup heater) is used to support the Daikin Wärmeerzeuger to generate heat. Backup heater Optional electric ancillary heater for general support of the Daikin Wärmeerzeuger during heat gener- ation. Circulation circuit Is an optional ancillary circuit in the hot water circuit which serves to ensure that hot water flows out of the discharge point as soon as the tap is turned on.
Page 51
The inflow target temperature for temperature control in the heating unit is calculated from the perature regulation measured value for the external temperature and a defined heating curve. Daikin Altherma EHS(X/H) Operating instructions Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Time period Monday Tuesday Wednesday Thursday Friday Saturday Sunday Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab. 10-2 Individual settings in the hot water timer programmes Operating instructions Daikin Altherma EHS(X/H) Daikin Altherma integrated solar unit 008.1420944 – 05/2014...
Comments setting Parameter Tab. 10-4 Individual parameter modifications 10.2.1 Data bus addresses RoCon appliance Data bus address Comments Tab. 10-5 Data bus addresses in the RoCon system Daikin Altherma EHS(X/H) Operating instructions Daikin Altherma integrated solar unit 008.1420944 – 05/2014...