7 Installing the Outdoor Unit
Refrigerant piping configuration, allowable piping lengths, and allowable height
differences
Make sure that the refrigerant piping lengths and height differences are within the following ranges.
Piping side
Cooling/heating mix operation units require BS units (units that allow switching between cooling and heating
mode).
You can switch between cooling and heating on each BS unit.
Outdoor
unit
REFNET Joint
BS unit
Allowable piping lengths and allowable height differences
Maximum allowable length *1
Actual length
170 m or less
200 m or less
*1: Piping length from the outdoor unit to the farthest indoor unit
*2: First branch as seen from the outdoor unit
*3: BS units may be installed anywhere between the first branch and the indoor unit if that length is within 60 m.
However, the height difference between BS units should not exceed the value of H2 (m).
the value of H2 given by the following formula.
When
is within the range of 40 to 60m: H2=37-
2
When
is within the range of 60 to 90 m: H2=11-
2
What is the equivalent piping length?
Equivalent length: the sum of the actual piping length plus the straight piping length equivalents of
Type
L joint
REFNET Joint
REFNET Header
Device Overview
REFNET Header
Indoor unit
Indoor unit
Indoor unit
Range B
Allowable height differences
Equivalent
Height difference between
length
outdoor and indoor units
50 m or less
is over 40 m, use the height difference between the outdoor and indoor units should not exceed
2)
11
20
7
60
the resistance of the respective parts of REFNET Joints and Headers and BS
units.
Pipe diameter
0.16
0.18
0.5
BSGQ100/160PV1
BS unit
1.0
BSGQ250PV1
3 pipes portion (suction gas pipe, discharge gas pipe, fluid pipe)
2 pipes portion (suction gas pipe, fluid pipe)
BS unit
BS unit
BS unit
Indoor unit
Indoor unit
Indoor unit
Range B
Range A
Height difference between
indoor units: H2
*4
15 m or less
×
(m)
2
×
(m)
2
0.2
0.25
0.35
0.4
6.0
15.0
– 12 –
Installation Work Manual
Note: No branch can be added downstream
REFNET Header
of the REFNET Header.
BS unit
BS unit
Indoor unit
Indoor unit
Range B
026723-01E
Height differences
between BS units
after the first branch
*4
15 m or less
90 m or less
0.45
0.5
0.55
0.65
*3
*2
0.75
0FGHP-EN0801 DGJ002