Inspecting The Heaters - Daikin GYEQ20AN Service Manual

Gas heat pump air conditioner heat recovery r-410a 50 hz
Table of Contents

Advertisement

Inspecting the Outdoor Unit

1.36 Inspecting the Heaters

Measure the resistance between terminals.
Measuring points
Between terminals
Measure the resistance between terminals.
Measuring points
Between terminals
Measure the resistance between terminals.
Measuring points
Between terminals
201
Inspecting the oil separator heater
Inspecting the accumulator heater
Inspecting the oil return heater
Measured value
570 Ω ±7%
Measured value
890 Ω ±10%
Measured value
5000 Ω ±7%
SiAUY361411EA
Parts Inspection