Inspecting The Starter System - Daikin GYEQ20AN Service Manual

Gas heat pump air conditioner heat recovery r-410a 50 hz
Table of Contents

Advertisement

Inspecting the Outdoor Unit
1.2

Inspecting the Starter System

Transformer
transformer
Self-starter
∗ This should be tested approximately 10 minutes after stopping (because the voltage
1. Using a tester, check if the output voltage requirements specified above are met.
2. If the voltage is significantly different than specified above, stop the system using the
3. If the harness and connectors are OK, then check each component.
[Note] Perform voltage checks by applying a tester to the back face of each connector, rather
Inspect the fuses on the harness to make sure they are not blown.
Inspect the transformer by measuring the resistance between its terminals.
Between red and black terminals on the primary side
Between blue terminals on the secondary side
∗ At 20°C (reference value)
Inspect the reactor by measuring the resistance between its terminals.
∗ At 20°C (reference value)
171
Activation timing
Transformer relay (RY8)
ON
OFF
Starter relay (RY3)
ON
OFF
Output voltage
Parts to
Measuring points
inspect
Between power supply circuit
relay
board's RY8 terminals
Starter
Between R and T terminals on
the primary side
Between S terminal and
ground
motor
Between B terminal and
ground
immediately after stopping will be the same as while running).
onboard checker and wait for 5 minutes; then, with the power OFF, check the harness for
continuity and the junction connectors for contact failure using a tester.
than unplugging the connector.
Fuses on the harness
Part
Purpose
On the
For S terminal
harness
For M terminal
Inspecting the starter transformer
Measuring points
Inspecting the reactor
Measuring points
GYEQ20AN
Between terminals
GYEQ30AN
After approx. 10 min
Power
System
Startup
System
ON
startup
complete
stop
During system stop After
startup (while running)
During stop: No continuity
While running: Continuity exists
During stop: 0 V
While running: 200 V AC
During stop: 0 V
While running: 0 V
During stop: 0 V
While running: 12 V DC
32 V DC/30 A
32 V DC/3 A
Model
Measured value (Ω)
SiAUY361411EA
Actuator
Actuator
check
check
CH01 : ON
CH01 : OFF
023303-00E
At system startup
(with actuator CH01
Continuity exists
Capacity
Measured value
520 mΩ
40 mΩ
0.17
0.06
ON)
200 V AC
12 V DC
12 V DC
Parts Inspection