■Input dark test execution setting
Set whether to perform the input dark test function of the diagnostic function in the safety remote I/O module in units of 1
point.
Module
Input module
Output module
I/O combined module
When "Wiring selection of input" is set to "0: Not used" or "3: General single", this parameter is ignored.
■Input dark test pulse OFF time setting
Set the width of the OFF pulses that the terminals T0 and T1 output, on a module-by-module basis.
Module
Input module
Output module
I/O combined module
When "Wiring selection of input" is set to "0: Not used" or "3: General single", or when "Input dark test
execution setting" is set to "1: Do not perform", this parameter is ignored.
■Number of pulse output for input dark test
Set the number of pulse output for input dark test on a module-by-module basis.
Module
Input module
Output module
I/O combined module
When "Wiring selection of input" is set to "0: Not used" or "3: General single", or when "Input dark test
execution setting" is set to "1: Do not perform", this parameter is ignored.
APPX
146
Appendix 4 Remote Buffer Memory
Address (hexadecimal)
Name
0160H to 0167H
Input dark test execution setting X0 to X7
0160H to 0167H
Address (hexadecimal)
Name
0170H
Input dark test pulse OFF time
0170H
Address (hexadecimal)
Name
0171H
Number of pulse output for input dark
test
0171H
Setting range
0: Perform
1: Do not perform
Setting range
0: 400s
1: 1ms
2: 2ms
Setting range
0: 1 time
1: 2 times
2: 3 times
Default value
0: Perform
Default value
0: 400s
Default value
0: 1 time