8.
Clicking the [Execute] button displays a confirmation window. Check the contents and click the [Yes] button. The
SAFETY LED of the selected safety remote I/O module starts flashing. Visually check that the safety remote I/O module
on which the SAFETY LED is flashing is installed on the desired position. At the same time, visually check that the
SAFETY LEDs of other safety remote I/O modules not targeted for the position checking are not flashing.
9.
After checking the safety remote I/O module position is completed, select "Stop of checking the module position" in
"Method selection" on the "Command Execution of Slave Station" window and click the [Execute] button.
10.
Clicking the [Execute] button displays a confirmation window. Check the contents and click the [Yes] button. The
SAFETY LED of the safety remote I/O module turns off.
11.
Perform the operations from "Start of checking the module position" to "Stop of checking the module position" for all
safety remote I/O modules connected.
7 SETTINGS
68
7.3 Safety Communication Setting
: On
: Flashing
: Off
: On
: Flashing
: Off