■Safety approval code
Set a value that identifies the individual safety remote I/O module. Set a value that does not overlap with those of other safety
remote I/O modules, such as a MAC address.
*1 When setting a MAC address, set the lower eight digits of the MAC address.
Address (hexadecimal)
0002H
0003H
■Communication speed setting
Set a communication speed with which the safety remote I/O module links up.
Address (hexadecimal)
000BH
Parameter data per module
■Wiring selection of input
Set the input wiring method in units of 1 point.
Module
Input module
Output module
I/O combined module
• When "Wiring selection of input" Xn (n: even number) is set to "1: Safety double wiring (NC/NC)", Xn+1, the
partner of Xn, is automatically set to "1: Safety double wiring (NC/NC)", and no other settings are possible.
• When Xn (n: even number) in "Wiring selection of input" is set to "0: Not used", "2: Safety single", or "3:
General single", set Xn+1, the partner of Xn, to other than "1: Safety double wiring (NC/NC)". When "1:
Safety double wiring (NC/NC)" is set, a parameter data error (wiring selection of input) (error code: 0560H)
occurs when "Write to PLC" is executed.
• For unused input terminals, set "0: Not used" in "Wiring selection of input".
• When "Fast logic pattern setting" is set to other than "0: Not used", this parameter is ignored.
■Input response time
Set the input response time of the input signal in units of 1 point.
Module
Input module
Output module
I/O combined module
• Select a longer time than the input dark test pulse OFF time for the parameter. When "1: Do not perform" is
selected for "Input dark test execution setting", a shorter time than the input dark test pulse OFF time can be
set for the parameter.
• When "Wiring selection of input" is set to "0: Not used", this parameter is ignored.
APPX
144
Appendix 4 Remote Buffer Memory
*1
Name
Safety approval code (lower 16 bits)
Safety approval code (upper 16 bits)
Name
Communication speed setting
Address (hexadecimal)
Name
0110H to 0117H
Wiring selection of inputs X0 to X7
0110H to 0117H
Address (hexadecimal)
Name
0120H to 0127H
Input response time X0 to X7
0120H to 0127H
Setting range
00000000H to FFFFFFFFH
Setting range
0: 1Gbps
1: 100Mbps
2: Automatic
Setting range
0: Not used
1: Safety double wiring (NC/NC)
2: Safety single
3: General single
Setting range
0: 1.0ms
1: 1.5ms
2: 5ms
3: 10ms
4: 20ms
5: 50ms
6: 70ms
Default value
FFFFFFFFH
Default value
0: 1Gbps
Default value
0: Not used
Default value
0: 1.0ms

Hide quick links: