Performance Specifications; Input Module - Mitsubishi Electric CC-Link IE-NZ2GNSS2-8D User Manual

Tsn remote i/o module with safety functions
Table of Contents

Advertisement

3.2

Performance Specifications

Input module

NZ2GNSS2-8D DC input module
Item
Station type
Authentication Class
Network topology
Number of input points
Rated input voltage
Rated input current
Maximum number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input circuit response time
OFFON
ONOFF
Safety remote station safety cycle time
Communication path response time
Safety remote station refresh response processing time
Safety remote station input response time
External power supply for
Voltage
*2
input part
Current
Protection function
Power supply current for input device (COM+)
Input type
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
External interface
Communication part
Module power supply part
I/O part, external power
supply part
Applicable wire size
Terminal block for module
power supply and FG
I/O terminal block
Applicable solderless
Terminal block for module
*3
terminal
power supply and FG
I/O terminal block
Multicast filter
Cyclic transmission
RX/RY points
RWr/RWw points
SA\X / SA\Y points
*2*4
Module power supply
Voltage
Current
Protection function
Fuse
Safety element
NZ2GNSS2-8D
Remote station
Authentication Class B
Line topology, star topology, mixture of star topology and line topology, ring topology
Single wiring: 8 points, double wiring: 4 points
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
7.3mA TYP. (for 24VDC)
100%
12VDC or higher/3mA or higher
5VDC or lower/1.3mA or lower
2.6k
0.4ms or less (24VDC)
2.0ms
0.3ms
Safety remote station safety cycle time + Communication path response time
Input circuit response time + Input response time (1ms, 1.5ms, 5ms, 10ms, 20ms, 50ms, 70ms)
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
100mA
External power supply overvoltage protection function
0.4A/1 terminal
Negative common type
510VAC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
Input 8 points/common (spring clamp terminal block)
RJ45 connector
Terminal block for module power supply and FG (2-piece spring clamp terminal block (push-in))
40 points, 2-piece spring clamp terminal block (push-in)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
Stranded wire: 0.5 to 1.5 (20 to 16 AWG)
Page 44 Applicable solderless terminal
Page 49 Applicable solderless terminal
*1
Available
16 points
4 points
SA\X: 16 points
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
160mA
Module power supply overvoltage protection function, module power supply overcurrent protection
function
1.6A (user-unchangeable)
Type B, HFT = 1, SC 3
*1
3 SPECIFICATIONS
3.2 Performance Specifications
3
19