Error code
Classification
(hexadecimal)
*1
0564H
Moderate error
*1
0580H
Moderate error
*1 Detailed information of the error is stored in Detailed Information in Error history data. For detailed information, refer to the following.
Page 122 Detailed information
When multiple errors have occurred, only the latest error code is stored in Error code (RWr1). The errors that
occurred before can be checked by executing "Error History" of the "CC-Link IE TSN/CC-Link IE Field
Diagnostics" in the engineering tool. For the error history, refer to the following.
Page 117 Checking by using CC-Link IE TSN/CC-Link IE Field diagnostics
However, when a moderate error occurs during a major error occurrence, the error code of the major error will
remain in Error code.
Moreover, when a minor error occurs during a moderate error occurrence, the error code of the moderate
error will remain in Error code.
Error name
Description and cause
Parameter data error
An incorrect value or parameter
(input response time)
data out of the range is set.
Parameter data error
An incorrect value or parameter
(wiring selection of
(wiring selection of output) out of
output)
the range is set.
Action
• Correct the module parameter settings (input
response time) and module configuration.
• When "0: Not used", "2: Safety single", or "3: General
single" is set to Xn (n: even number) in "Wiring
selection of input", set a value other than "1: Safety
double wiring (NC/NC)" for Xn+1.
• Set the input response time so that it is longer than
the input dark test pulse output time.
Pulse output time for the input dark test = Pulse OFF
time for the input dark test  ((Number of pulse outputs
for the input dark test  2) - 1)
• When the parameters are set again and the
parameter setting has succeeded, the module will
recover from this error.
• Correct the module parameter settings (wiring
selection of output) and module configuration.
• When "0: Not used" or "2: Safety single" is set to Yn
(n: even number) in "Wiring selection of output", set a
value other than "1: Safety double wiring (Source/
Source)" for Yn+1.
• When the parameters are set again and the
parameter setting has succeeded, the module will
recover from this error.