Mitsubishi Electric CC-Link IE-NZ2GNSS2-8D User Manual page 85

Tsn remote i/o module with safety functions
Table of Contents

Advertisement

Operation when fast logic output is off
■When fast logic interlock is enabled
When all the corresponding output signal points are turned off by the fast logic function, the fast logic READY (SA\XC) is
turned off, the fast logic function stops operating, and the fast logic interlock state is entered.
When restarting the fast logic function, turning off and on the fast logic initial request flag (SA\Y8) and fast logic start flag
(SA\Y9), or operating the reset signal X7 and start signal X6 causes fast logic READY (SA\XC) to turn ON and the operation
to resume.
The operation when the fast logic pattern setting is Pattern 2 is shown below.
Module operation mode
Input signal (X0, X1)
Input signal (X2, X3)
Input signal (X4, X5)
Output signal (Y0, Y1)
Safety output enable signal
(SA\Y0, SA\Y1)
Fast logic READY (SA\XC)
Fast logic initial request flag
(SA\Y8), Reset signal (X7)
Fast logic start flag (SA\Y9),
Start signal (X6)
Fast logic initial completed flag
(SA\XD)
Executed by the program
(1) When the fast logic output is not off, even if the fast logic initial request flag (SA\Y8) and fast logic start flag (SA\Y9) are operated, the fast logic initial
completion flag (SA/XD) does not change.
(2) Turning off and on the fast logic initial request flag (SA\Y8) when fast logic output is off causes fast logic initial processing to be performed. When initial
processing is completed, the fast logic initial completion flag (SA\XD) turns ON.
(3) When the fast logic start flag (SA\Y9) is turned off and on while the fast logic initial completion flag (SA\XD) is on, fast logic READY (SA\XC) turns on, fast
logic initial completion flag (SA\XD) turns off, and the fast logic function is enabled.
The operation of the fast logic function can be resumed by operating reset signal X7 and start signal X6 only
when the fast logic function stops operating during safety communications return (fast logic interlock state).
After safety communications changes from disconnected to connected, operate the fast logic initial request
flag (SA\Y8) and fast logic start flag (SA\Y9) to restart the fast logic function.
ON
OFF
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
(1)
OFF
(2)
OFF
Safety operation mode
(3)
ON
8
8 FUNCTIONS
83
8.4 Safety Output

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc-link ie-nz2gnss2-8teCc-link ie-nz2gnss2-16dte

Table of Contents