SET COMMUNICATION:

This section define the fundamental communication parameters of two buses, BACnet and DMX.
By Pressing the
"Set
Communication" button from the main window for SW67704 (Fig. 2) the
window "Set Communication" appears (Fig. 3).
The window is divided in three sections, one for selecting the type of BACnet (in relation to the device
bought), one for the BACnet parameters and the other for the DMX parameters.
In the section "BACnet Type" is possible to select the type of BACnet to use from:
BACnet/IP (it uses Ethernet);
BACnet MS/TP (it uses RS485).
If selected "BACnet/IP" the means of the fields for "BACnet" are:
In the field
"IP
ADDRESS" the IP address to assign to the converter is defined;
In the field
"SUBNET
Mask" the SubNet Mask of the converter is defined;
In the field "GATEWAY" the default gateway of the network is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field "Port" the port used for BACnet communication is defined. The default port used for
BACnet communication is 47808, but it is possible to insert any value (except 10000 and
10001);
In the field
"BACnet Device
In the field
"Device
Identifier" the number to the BACnet node (used for the Device Identifier)
is defined.
The means of the fields for "DMX" section are:
In the field "DMX" it is possible to define if the converter will act as DMX controller ("OUT") or
as DMX device ("IN");
In the field
"Channel
Number" the number of channels of the DMX side is defined (up to 512
channels).
ADFweb.com S.r.l.
Name" the name to the BACnet node is defined;
User Manual DMX / BACnet Master
Document code: MN67704_ENG
Revision 1.000
Figure 3: "Set Communication" window