ADF Web HD67704-IP-B2 User Manual page 20

Dmx / bacnet master - converter
Table of Contents

Advertisement

Industrial Electronic Devices
Figure 4b: "Set BACnet Access
The means of the fields in the window (Write) are the following:
In the field
"IP Address /
In the field
"Object
Type" the object to be written is defined;
In the field
"Data
Type" the type of data to write is defined;
In the field "Instance" the instance number of the object is defined;
In the field "Property" the property to be read is defined;
In the field "Priority" the priority of the BACnet request is defined;
By checking the field
"En
Address (D Adr). These informations are used for make a request to other segments of network (through a BACnet router);
In the field
"D
Net" the destination network (from 1 to 65535) is defined;
In the field
"D
Len" the length of "D Add" field (1 or 2 or 6) is defined;
In the field
"D
Adr" the address of the endpoint is defined. If "D Len" is '1' it is possible to insert a number from 1 to 255; if "D Len"
is '2' it is possible to insert a number from 1 to 65535; if "D Len" is '6' it is possible to insert an IP and port in this format
"192.168.2.188:47808";
By checking the field "Change" the BACnet write request is made only if DMX data are changed; otherwise (if is selected the field
"Timer") it is sent cyclically, using the "Poll Time";
ADFweb.com S.r.l.
BACnet Write" window
ID" the IP address / ID of the slave that contains the data to be written is defined;
Dest" it is possible to enable the Destination Network (D Net), Destination Length (D Len) and Destination
User Manual DMX / BACnet Master
Document code: MN67704_ENG
Revision 1.000
Page 20 of 28