Figure 4-35. Input Calibration, Minimum Point
4. Click Start Calibrate to begin calibration.
5. Once the raw minimum value stabilizes, click Freeze Count to capture the data.
6. Enter the new minimum value. If the data captured as the raw minimum was 3.98
mA, but it should be reading 4 mA, enter 4 in the Enter new Min Value textbox.
a. If there is a problem with the data, the user has the option to abort the
calibration by clicking the Abort CAL button, and can return to the previous
screen by pressing the Back button.
b. To recalculate the point, click Start Calibrate before clicking the Submit
button.
c. If the point data is satisfactory, click Submit to save and Next to move to the
next point.
In a 2-point calibration, the next screen will calibrate the maximum
values.
In a 3-point calibration, the next screen will calibrate the mid-point
values. Submit that information and click the Next button to proceed to
the maximum point value screen.
7. Follow steps 4 – 6 to calibrate the remaining point(s).