4 .4 Electrical installation

4.4.1-1:

Wiring Terminal Blocks

4.4.4-1:
WARNING
Wiring diagram
4 .4 .1 Wiring Terminal Blocks
Remove panel covers and you will see the wiring
terminal block.
4.4.1-1
UPS Rating
5KVA/6KVA
8KVA/10KVA
The AC input block connects the two phase utility
supply, voltage and frequency is 88/152-155/269
Vac and 50/(60) Hz.
The AC output block connects the two phase
critical loads, voltage and frequency is 100/200
110/220 115/230 120/208 120/240 127/220VAC
and 50/(60) Hz.
The battery connector connects the external
battery module, voltage is +/- 120VDC.

4 .4 .2 AC source connection

Connect AC input to the AC power source. The
sequence of two phase can be connected freely.
The wrong sequence will not alarm for 2-phase
UPS system when the UPS is powered. A common
N (neutral) wire must be securely connected for
proper UPS operation. A warning message will
indicate if the N wire is missing or not connected
properly. The UPS will show warning message as "
Warning 1C". Then, the UPS will transfer to battery
mode if battery pack is connected or transfer to
standby mode and no output if no battery pack is
connected.

4 .4 .3 DC source connection

Connect the UPS to the ±120V battery module
using a dedicated cable. Ensure that the ports on
the back of the UPS and the battery pack are
properly connected. Press the battery start
button and the machine will enter Standby Mode.
If the machine is not powered on within 1 minute,
it will automatically shut down.
• MAKE SURE THE MAINS SUPPLY AND THE TOTAL LOAD DEMAND ARE WITHIN UPS SPECIFICATIONS.
• BEFORE WIRING, MAKE SURE THE AC INPUT AND BATTERY POWER ARE COMPLETELY CUT OFF.
• MAKE SURE THE BREAKERS, INCLUDING AC INPUT BREAKER, AC OUTPUT BREAKER AND DC BREAKER,
ARE ALL IN THE OFF POSITION.
INPUT~
OUTPUT~
L1
N
L2
L1
N
L2
Min
Number
Terminal
conductor
and size of
size(mm2)
terminal
AC INPUT
8-M5-Bolt
GROUND
6
mounting
AC OUTPUT
AC INPUT
8-M6-Bolt
GROUND
8
Mounting
AC OUTPUT

4 .4 .4 Recommended cable sections and fuse ratings

When selecting the cable cross-sections and the
protective devices, follow the recommendations
in below table or follow local standards.
Table 2: Cable sections and fuse ratings
5 kVA
SINGLE INPUT FEED
Input CB:Type
2 x 40A
D[L1,L2]
Input cable A
4 x AWG 10 4 x AWG 10 4 x AWG 8 4 x AWG 8
[L1, L2, N, PE]
Torque
Output cable D
Nm
4 x AWG 10 4 x AWG 10 4 x AWG 8 4 x AWG 8
[L1, L2, N, PE]
(lb in)
External Battery
2 x 63A
CB:Type K [+,-]
2.2(20)
2.2(20)
4.4.4-1
THE CABLE FOR 5K/6K SHOULD BE ABLE
TO WITHSTAND OVER 30A CURRENT. IT IS
RECOMMENDED TO USE 10AWG OR
THICKER WIRE FOR SAFETY AND
NOTE
EFFICIENCY.
THE CABLE FOR 8K/10K SHOULD BE
ABLE TO WITHSTAND OVER 53A
CURRENT. IT IS RECOMMENDED TO USE
8AWG OR THICKER WIRE FOR SAFETY
NOTE
AND EFFICIENCY.
THE SELECTIONS FOR COLOR OF WIRES
SHOULD BE FOLLOWED BY THE LOCAL
ELECTRICAL LAWS AND REGULATIONS.
NOTE
6 kVA
8 kVA
10 kVA
2 x 40A
2 x 63A
2 x 63A
2 x 63A
2 x 63A
2 x 63A
I I n n p p u u t t
F F i i l l t t e e r r
A A C C
D D C C
D D C C
A A C C
O O u u t t p p u u t t
F F i i l l t t e e r r