Technical Specifications; General Product Data; Utility Input - ABB HiPerGuard MV UPS User Manual

Hide thumbs Also See for HiPerGuard MV UPS:
Table of Contents

Advertisement

39

Technical specifications

General product data

Product class
General
Rated Voltage
Rated apparent power
Rated active power
Hard parallel configuration
Performance
Efficiency
Dynamic output perfor-
mance
Architecture
Table 5.01: HiPerGuard
MV UPS General Data

5.1 Utility input

Input
Voltage tolerance
Rated frequency
Frequency tolerance
Displacement power factor at
supply
Battery charging current
Power Distribution system
Current distortion THDi
Table 5.02: HiPer-
Guard MV UPS Input
specifications
7.2 kV IEC
12kV IEC
6-6.6kV
10-11 kV
2250kVA
2250kW
Up to 10 units
98% for 50% to 100% loading
96% for 25% to 50% loading
In line with IEC62040-3 VI SS 111
ZISC enabled line interactive
±10 %
50 Hz/60 Hz
± 2 %
> 0.96
10-20%
IT, 3-Wire Input
< 3%
15 kV ANSI
24kV IEC
12.47-13.8kV
20-22kV
From nominal voltage
From rated frequency
Under nominal conditions
Grid supplied on top of the load current
Please contact ABB for other distribution
systems
Full linear load, under nominal conditions,
operating on power conditioning mode.
Single unit
Load power
factor 1.0
Under nomi-
nal conditions