5.2.6 Multiple Lane Conduit Layout
Multiple lanes require additional conduits. The following illustration represents a typical multiple
lane conduit layout.
Always refer to site specific drawings for correct detail and number of conduits.
Rules to follow when running conduit to multiple lanes:
Always make sure to run minimum of two (2) 1 1/2" conduits between each lane.
Always verify the proper number and location of conduits for Mains Power, ACS, Fire
Alarm, Remote Control Panels and any other interface equipment that may integrate with
the Speedlane units.