cONNecTION Of THe POWer UNIT
4.2.5.8 Wiring of the motor
➀
➁
Control
P A/K
9
5
X1C
10
6
U
X1A
V
W
Figure 17:
Wiring of the motor
NOTICE
4.2.6 connection of a braking resistor
cAUTION
4.2.6.1 Terminal strip X1B connection braking resistor
X1b
R -- ++ U V W
Figure 18:
Terminal block X1B Connection of a braking resistor
48
Legend
➂
④
①
②
U
V
③
W
④
connection of the temperature monitoring
•
Do not lay the connection cable of the motor temperature detection
(also shielded) together with the control cable !
•
The connection cable of the temperature detection inside the motor
cable is only permissible with additional shielding (double shielding) !
•
The input of the temperature detection has basic isolation.
Not fall below the minimum braking resistor value! Falling below
the minimum braking resistor value destroys the braking transistor of
the drive converter.
KEB COMBIVERT
Apply motor cable, shielding on both sides over a
large surface on the function earth (screening shield
or mounting plate)
Three-phase motor
Temperature monitoring (optional)
=>
Instructions for use „Control unit"
Name
function
++
Connection braking resistor
R
Type
Screwdriver blade
Stripping length
Wire cross-section
without wire-end ferrule
with wire-end ferrule
Push-In spring connection
08 x 4.5
12 mm
AWG 24-8
0.5...10 mm²
1.5...6 mm²