KEB COMBIVERT S6 Instructions For Use Manual page 61

Hide thumbs Also See for COMBIVERT S6:
Table of Contents

Advertisement

UL MArKING
• WARNING – The opening of the branch circuit protective device may be an indica-
Branch Circuit Protection for series S6 housing size 4
I) Class CC or J, fuses; not more than 5000 rms Symmetrical Amperes (SCCR 5kA);
Class CC, fuses; not more than 30000 rms Symmetrical Amperes (SCCR 30kA):
The voltage rating of the external fuses shall be at least equal to the input voltage of the
drives.
II) Listed (NKHJ, NKHJ7/CSA Certified), Type E Self Protected Manual Motor Control-
lers, not more than 5000 rms Symmetrical Amperes (SCCR 5kA), Type and manufactur-
er and electrical ratings as specified below:
200-230V Models:
cat. No.
480V Models:
cat. No.
N/A = not applicable
tion that a fault current has been interrupted. To reduce the risk of fire or electrical
shock, current-carrying parts and other components of the controller should be ex-
amined and replaced if damaged. If burnout of the current element of an overload
relay occurs, the complete overload relay must be replaced."
And
ATTENTION – LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU
CIRCUIT DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE
D'UN COURANT DE DÉFAUT. POUR LIMITER LE RISQUE D'INCENDIE OU DE
CHOC ÉLECTRIQUE, EXAMINER LES PIÈCES PORTEUSES DE COURANT ET
LES AUTRES ÉLÉMENTS DU CONTRÔLEUR ET LES REMPLACER S'ILS SONT
ENDOMMAGÉS. EN CAS DE GRILLAGE DE L'ÉLÉMENT TRAVERSÉ PAR LE
COURANT DANS UN RELAIS DE SURCHARGE, LE RELAIS TOUT ENTIER DOIT
ÊTRE REMPLACÉ.
cat. No.
Housing
12S6
04
13S6
04
14S6
04
Housing
Manufacturer
12S6
13S6
04
14S6
Housing
Manufacturer
12S6
13S6
04
14S6
Input Voltage [Vac]
200-230V / 3ph
480 / 3ph
200-230V / 3ph
480 / 3ph
200-230V / 3ph
480 / 3ph
Type
Eaton
PKZM0 32-E
N/A
N/A
Type
Eaton
PKZM0 32-E
N/A
N/A
maximum fuse size [A]
15
20
25
rating
200V/3ph, 7.5 hp
230V/3ph, 10 hp
N/A
rating
480Y/277V/3ph, 20 hp
N/A
61