brAKe cONTrOL AND TeMPerATUre DeTecTION

4.4.2 Specification and connection of the temperature detection

DANGer
NOTICE
A switchable KTY84/PTC evaluation is implemented in the COMBIVERT. The desired
operating mode can be adjusted by software (dr33).
Operating mode (dr33)
0
1
2
3
4
5
Table 30:

4.4.2.1 Operation without temperature detection

Use of the COMBIVERT without evaluation of the temperature input:
or
Use only sensors with safe isolation !
Danger to life due to electric shock !
Malfunctions due to incorrect cable or laying!
Malfunctions of the control due to capacitive or inductive coupling.
► Do not lay cables of the motor temperature sensor (also shielded)
together with the control cable !
► Cables of the motor temperature sensor inside the motor cable only
permissible with double shielding !
resistance
at too short resistance
498 Ω
KTY84/130
1 kΩ
1,722 kΩ
PTC in accordance
0.75...1.5 kΩ (reset resistance)
with DIN EN 60947-8
1.65...4 kΩ (tripping resistance)
(standard)
by encoder
digital by the encoder channel
820 Ω
KTY83/110
1670 Ω
2535 Ω
1000 Ω
PT1000
1385 Ω
1758 Ω
free-definable sensor characteristic
at too high resistance
Specification of the temperature input
Deactivate the evaluation (pn12 =7).
Install bridge between terminal TA1 (X1C.9) and TA2 (X1C.10) (dr33=1).
Temperature/state
short circuit
0°C
100°C
200°C
undefined
undefined
0°C
100°C
175°C
0°C
100°C
200°C
no connection