The time since the error occurred is measured in Days:Hours:Minutes:Seconds
saved in the permanent memory of the device at intervals of 1 hour. It only includes the time
when the device is energized. The counter continues when the device is switched back on.
The error symbol is no longer displayed after you read the error record.

6.6.2 Error handling

Types of error message
Type of error
Error
Warning
Description of errors and corrective actions
Error Message
Current output
Current output saturated at
maximum value
Current output saturated at
minimum value
External influences
Temperature out of range for
NAND Flash
Self-test manager
Self Test has failed
34-VF-25-31 iss.4 GLO December 15 US
Days:Hours:Minutes:Seconds
Days:Hours:Minutes:Seconds
Days:Hours:Minutes:Seconds.The error is
Error
code
E
If an error message is displayed in the error record (menu
item B.2.6), the measured value is not correct. The output
current goes to the value set in menu items C.3.5 Error
Handling (Output 1) and C.4.5 Error Handling (Output 2). For
more data, refer to
Advanced Setup.
W
If a warning message continues, the measured value will no
longer be correct.
Error
Description
code
W
The output is at its maximum
output value (20 or 20.5 mA)
because the measured value
is now out of the
measurement range.
W
The output is at its minimum
output value (4 or 3.8 mA)
because the measured value
is now out of the
measurement range.
W
The ambient temperature is
outside the given range. This
can cause loss or corruption
of data.
E
The device's self-test failed.
This can occur if the ambient
temperature is not between
-40...+80°C / -40...+175°F.
One of the electronic boards
is defective.
www.honeywell.com/ps
OPERATION
Description
Function description
on page 53, table C.
Corrective action
Fill the silo or remove some
of the product until the level
is back in the configured
range.
Fill the silo or remove some
of the product until the level
is back in the configured
range.
De-energize the device until
the ambient temperature is
back in the given range. If the
problem continues, contact
the supplier.
Energize the device when the
ambient temperature is
between -40...+80°C /
-40...+175°F. If the device
does not operate correctly,
contact the supplier.
Replace the electronics
block. For more data, refer to
Replacement of the complete
electronic module
6
on page 80.
73