6.4.6 How to configure the device to measure volume or mass

The device can be configured to measure volume or mass. You can set up a strapping table in the
conversion table in the device's Quick Setup
How to create a volume or mass table.
• Go to Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion.
Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion
• Complete all the steps in the set-up procedure.
The device creates a table of up to 50 pairs of data (level – volume or level – mass). The
reference point for the table is the silo bottom (as given in menu item C.1.2 Tank Height).
INFORMATION!
You can also create customized length and conversion units (free units) in the Conversion
procedure.
INFORMATION!
When you create a table, get more conversion data for parts of the silo where there are:
Surfaces with curves.
Sudden changes in the cross section.
This will make volume measurement more accurate.
Figure 6-6: A plot of points for a volume or mass table
1 Silo with reference points
2 Silo model with plotted points
34-VF-25-31 iss.4 GLO December 15 US