INSTALLATION
SMARTLINE® RM60 (FMCW)
3
If the antenna is smaller than the process connection:
• Make sure the flange on the nozzle is level.
• Make sure that you use the applicable gasket for the flange dimensions and the process.
• Align the gasket correctly on the flange facing of the nozzle.
• Lower the antenna carefully into the silo.
• Tighten the flange bolts.
i
Refer to local rules and regulations for the correct torque to apply to the bolts.
Figure 3-9: How to attach the device if the antenna is larger than the process connection
Equipment needed:
• 3 mm Allen wrench (not supplied)
WARNING!
If you attach the antenna in a closed space, make sure that there is a good airflow in the area.
Make sure that a person not in the silo can always hear you.
If the antenna is larger than the process connection:
• Make sure the flange on the nozzle is level.
• Remove the antenna locking screw from the part below the flange.
• Remove the antenna from the part below the flange.
• Align the gasket correctly on the flange facing of the nozzle.
• Put the device carefully on the silo flange. Do not attach the device flange to the silo yet.
• Attach the antenna to the device inside the tank. Go to the top of the tank.
• Lift the device a small distance. Attach the antenna locking screw to the part below the flange.
Tighten the antenna locking screw.
• Put the device carefully on the silo flange. Tighten the flange bolts.
34-VF-25-31 iss.4 GLO December 15 US
www.honeywell.com/ps
27