Honeywell SmartLine RM60 Handbook page 61

24 ghz non-contact radar (fmcw) level meter
Table of Contents

Advertisement

SMARTLINE® RM60 (FMCW)
Menu
Function
No.
C.3.5
Error Handling
Error Handling
Delay
C.3.6
HART Address
C.4 Output 2 (Passive)
C.4.1
Output
Function
C.4.2
4 mA Setting
C.4.3
20 mA Setting
C.4.4
Output Range
C.4.5
Error Handling
Error Handling
Delay
C.5 Device Setup
C.5.1
C.5.1
Display
Display
C.5.1
C.5.1
Display
Display
Settings
Settings
Settings
Settings
C.5.1.1
Language
C.5.1.2
Display Mode
C.5.1.3
Time Delay
Contrast
C.5.1.4
Length Unit
34-VF-25-31 iss.4 GLO December 15 US
Function description
This sets the behaviour of current
output 1 if an error occurs. Hold means
that the output current stays at the
value where the error occurred. Hold is
not available if 3.8...20.5 mA (NAMUR)
is the output range.
The time after which the current output
changes to an error value. It shows
that there is a measurement error.
Any HART® address greater than 0 will
activate HART® multidrop mode. The
current output stays constant at 4 mA.
Select an output function to scale the
current values. This is not displayed in
the operator mode.
3
Give a measurement value to 4 mA.
Give a measurement value to 20 mA.
Sets the effective range of output 2
either with or without over-run.
This sets the behaviour of current
output 2 if an error occurs. Hold means
that the output current stays at the
value where the error occurred. Hold is
not available if 3.8...20.5 mA (NAMUR)
is the output range.
3
The time after which the device shows
there is a measurement error. This
value is set in the output 1 menu.
To display the information you need,
To display the information you need,
To display the information you need,
To display the information you need,
refer to these menu items.
refer to these menu items.
refer to these menu items.
refer to these menu items.
Information can be displayed in any of
the 9 languages stored in the device. If
it is necessary to change the display
quickly to English, push [ ] for 3
seconds in operator mode.
The display screen status will change
after the time given in C.5.1.3. (time
delay). Disable
Disable switches off this
Disable
Disable
functionality, Auto-Off
Auto-Off switches off the
Auto-Off
Auto-Off
display and Default Screen
Default Screen
Default Screen will show
Default Screen
the selected default screen. To set to
the default screen, push [ ] for 1
second in the operator mode.
The time after which the display will
switch to the status set in C.5.1.2
(Display Mode).
The contrast control for the display
screen. You can select a shade of gray
between light gray (level 1) and black
(level 9).
The length unit displayed in operator
mode.
www.honeywell.com/ps
Selection list
3.6 mA, 22 mA, Hold
min.-max:
0...900 sec (seconds)
min.-max: 0...15
Level, Distance, Volume
(Mass), Ullage Volume (Ullage
Mass), Reflection
min.-max:
3
1
min.-max:
3
2
min.-max: 3.8...20.5 mA
(NAMUR), 4...20 mA
3
3.6 mA, 22 mA, Hold
Read only
3
English, French, German,
Italian, Japanese, Chinese
(simplified), Portuguese,
Russian, Spanish
Disable, Auto-Off,
Default Screen
1, 3, 5, 10 (minutes)
Level 1, Level 2, Level 3,
Level 4, Level 5, Level 6, Level
7, Level 8, Level 9
m, cm, mm, inch, ft,
ft-inch-1/16inch,
ft-inch-1/32inch, Free Unit
OPERATION
6
Default
22 mA
10 sec
0
Level
0 m / 0 ft
Depends on the
output function
4...20 mA
22 mA
Refer to
function C.3.5
Disable
1
Level 5
m
61