SMARTLINE® RM60 (FMCW)
Menu
Step
Function
No.
6
Tank Shape
7
Conversion Unit
8
Mass Table
Sub-
Conversion
menu
submenu
[Free Unit]
[Free Unit]
[Free Unit]
[Free Unit]
1
Do you want to use
free unit?
2
Custom. Length
Unit
3
Custom. Length
Ratio
4
Custom. Conv. Unit A non-standard conversion unit
5
No. of Entries
6
Volume/Mass
Table
...
Current changes
must be saved or
cancelled before
proceeding
A.1.5
A.1.5
A.1.5
A.1.5
Outputs
Outputs
Outputs
Outputs
1
Output 1: Output
Function
2
Output 1 (HART):
<Function> 4 mA
3
Output 1 (HART):
<Function> 20 mA
34-VF-25-31 iss.4 GLO December 15 US
Function description
The Wizard adds this step if you
select "Yes" in step 4. This sub-
procedure uses the
information given here to find
the volume. You have to type in
the tank shape, height, width
and length.
The conversion unit is given as
a volume if the product density
is given. If not, choose a mass
unit.
A table that converts product
level to product mass. If you
selected "Yes" in step 4, make
entries in the table in volume
units. Push[ ] or [ ] to select
a line and push [> > > > ] to change
values automatically supplied
by the device.
If you cannot find the units or
silo shape in the menu, you can
customize the conversion
table.
Select "Yes".
A non-standard length unit for
the conversion table. This is
defined by the supervisor.
The conversion factor between
the length unit selected in
C.5.1.4 (length unit) and C.5.1.7
(customer length unit). This
ratio is a multiple of 1 mm.
for the conversion table. This is
defined by the supervisor.
The number of lines in the
conversion table.
A table that converts product
level to another physical
parameter. Push[ ] or [ ] to
select a line and push [> > > > ] to
change values automatically
supplied by the device.
Follow this procedure to
Follow this procedure to
Follow this procedure to
Follow this procedure to
describe the output
describe the output
describe the output
describe the output
characteristics.
characteristics.
characteristics.
characteristics.
Select an output function to
scale the current values
(output 1). This is not displayed
in the operator mode.
This assigns a measurement
value to 4 mA (output 1).
This assigns a measurement
value to 20 mA (output 1).
www.honeywell.com/ps
OPERATION
Selection list
...
m3, L, US gal, GB gal, ft3,
bbl or Tons, kg, US Tons, GB
Tons
Yes, No
min-max: 1...99999
min-max: 0...50
Save, Cancel
3
Level, Distance, Volume
(Mass), Ullage Volume
(Ullage Mass), Reflection
min-max:
0...20 m / 0...65.62 ft
min-max:
0...90 m / 0...295.29 ft
6
Default
...
m3 or Tons
No
LEN_
FREE_
1
CO_FR_UN
2
Save
Level
0 m / 0 ft
Depends on
the output
function
55