Malfunctions
System faults
Voltage fluctuations
Total current consumption
Tab. 34 Fault clearance of system faults
9.2.3
Valve faults
In the event of a valve fault, only the faulty valve is deactivated in the status word. The red LED flashes
and error bit 3 in the status word becomes active. The valves without faults are not affected by this.
Valve faults can be identified by the fact that selected faulty valves are indicated as deactivated in the
status word and the red LED flashes.
Valve faults
–
Idling of the valve
–
Cable break at valve con-
nection
–
Current consumption of a
valve exceeds permissible
value
–
Valve short-circuit
Festo — VAEM-V-S8EPRS2 — 2020-07
Inspection interval
–
Constant review
–
At start-up
–
During the operating time
of the valves
Inspection interval
–
At start-up
–
At start-up
–
During the operating time
of the valves
Remedy
–
Check fixed power supply
–
Ensure constant nominal
voltage
At least 80% of the nominal
voltage
–
9.2.1 Resetting the
è
active error bit
–
Check the total current con-
sumption of the product.
Total current consumption
1.8 A
–
Check current consumption
of valves and adjust config-
uration parameters if neces-
sary
–
9.2.1 Resetting the
è
active error bit
Remedy
–
Check valve and wiring and
replace if necessary
–
Error in case of current
consumption after start
command
20 mA
<
(
100 ms)
>
–
9.2.1 Resetting the
è
active error bit
–
Check the current consump-
tion of the valve
–
Error in case of current
consumption during
tightening phase
1.35 A
>
<
27