Malfunctions
System faults
Voltage fluctuations
Total current consumption
Tab. 34 Fault clearance of system faults
9.2.3

Valve faults

In the event of a valve fault, only the faulty valve is deactivated in the status word. The red LED flashes
and error bit 3 in the status word becomes active. The valves without faults are not affected by this.
Valve faults can be identified by the fact that selected faulty valves are indicated as deactivated in the
status word and the red LED flashes.
Valve faults
Idling of the valve
Cable break at valve con-
nection
Current consumption of a
valve exceeds permissible
value
Valve short-circuit
Festo — VAEM-V-S8EPRS2 — 2020-07
Inspection interval
Constant review
At start-up
During the operating time
of the valves
Inspection interval
At start-up
At start-up
During the operating time
of the valves
Remedy
Check fixed power supply
Ensure constant nominal
voltage
At least 80% of the nominal
voltage
9.2.1 Resetting the
è
active error bit
Check the total current con-
sumption of the product.
Total current consumption
1.8 A
Check current consumption
of valves and adjust config-
uration parameters if neces-
sary
9.2.1 Resetting the
è
active error bit
Remedy
Check valve and wiring and
replace if necessary
Error in case of current
consumption after start
command
 20 mA
<
(
 100 ms)
>
9.2.1 Resetting the
è
active error bit
Check the current consump-
tion of the valve
Error in case of current
consumption during
tightening phase
 1.35 A
>
<
27