Additional Features; Remote Programming And Monitoring - Xantrex XFR 2800 Operating Manual

Xfr 2800 watt series programmable dc power supply
Table of Contents

Advertisement

Additional
Features
Switching Frequency
Output Hold-up Time
Maximum Voltage Differential from
either output to safety ground
Insulation Resistance
Isolation Voltage
Remote
Programming
and
Monitoring
Remote Start/Stop and Interlock
Remote Analog Programming (Full
Scale Input)
Remote Monitoring
Remote Programming and
Monitoring Accuracy
Maximum Remote Sense Line Drop
Compensation
Optional Isolated Program and
Readback (V&I)
Optional Digital Control
Release 2.1
Features and Specifications
nominal 31 kHz (62 kHz output ripple).
Greater than 10 ms with interruption of AC line,
for nominal AC input and full load.
±600 Vdc
Input to chassis: >30 MΩ, with 500 Vdc;
Output to chassis: >20 MΩ, with 1000 Vdc.
Input to output: 1350 Vac
2.5-15 V signal or TTL-compatible input,
selectable logic. TTL input impedance: 2 k (in
series with one diode drop).
Voltage and current programming inputs
(source must be isolated): 0-5 k, 0-10 k
resistances; 0-5 V, 0-10 V (default) voltage
sources. Input impedance (V and I):
approximately 100 k.
Output voltage and current: 0-5 V, 0-10 V
(default);
Output impedance (V and I): approximately
221 Ω.
Output short circuit current: approximately
50 mA.
1% zero to full scale output for the default
range.
5 V/line (Line drop is subtracted from total voltage
available at supply output.)
0-5 V (ISOL interface); input impedance: 200 k;
output impedance: 221 Ω.
RS-232, GPIB interfaces
Specifications
31

Hide quick links:

Advertisement

Table of Contents
loading