Figure 2.5 Typical Load Connection Hardware - Xantrex XFR 2800 Operating Manual

Xfr 2800 watt series programmable dc power supply
Table of Contents

Advertisement

Installation
Load Connection
7.5 V to 100 V Models The 7.5 V to 100 V models are equipped with output bus
bars. To make a typical load connection to a 7.5 V, 300 A power supply:
1. Strip the ends of the wires.
2. Remove the top part of the output cover. Do not remove the chassis-mounted part
3. Loosen wire clamp screws (part of strain relief). Do not disassemble the strain
4. Insert load wire in strain relief.
5. Install connectors to load wiring.
6. Fasten connectors to bus bars with 5/16 in. x 5/8 in. (M8 x 16 mm) screws,
7. Tighten the strain relief clamp.
8. Replace the top cover.
Note: Bus bar hole sizes are one of 0.343 in. (8.7 mm) D; two of 0.197 in. (5.0 mm) D.
Screw (2 places)
Wire connector (2 places)

Figure 2.5 Typical Load Connection Hardware

(For 7.5 V to 100 V models.)
48
of the cover.
relief.
5/16 in. (M8) flat washers, lock washers, and hex nuts as shown in Figure 2.5.
Hex Nut (2 places)
Lock Washer (2 places)
Flat Washer (2 places)
Assembled View
Operating Manual for XFR 2.8kW Series Power Supply