96
Appendix
10.1.2.1
PROFIBUS DP Fieldbus Coupler 750-333/040-000
The following assignment applies to the parameters of the I/O module when
using PROFIBUS DP and PROFINET IO fieldbus devices.
Tabelle 56: Specific module / channel parameters for 750-486/040-000
GSD File
Description
Number format
Noise filter
Signal type
Channel x
(x = 0...3)
Input filter
(25 Hz)
Channel x
(x = 0...3)
*)
Default setting
The fieldbus couplers allow module-specific parameterization of behavior at
diagnosis.
Table 57: General module / channel parameters
Parameter
Diagnosis
Channel x
(x = 0...3)
*)
Default setting
Manual
Version 1.0.0
750-486/040-000 4AI 0/4-20mA NE43 Ex i XTR
Value
*)
Twos complement
Sign magnitude
*)
deactivated
activated
deactivated
0-20 mA
4-20 mA
3.6-21 mA (Namur
*)
NE43)
*)
deactivated
activated
Value
*)
0 (disabled)
1 (enabled)
WAGO-I/O-SYSTEM 750 XTR
WAGO-I/O-CHECK
Description
Value
Number format Twos complement
Sign magnitude
Noise filter
Checkbox deactivated
activated
Signal type
deactivated
0-20 mA
4-20 mA
3.6-21 mA (Namur
NE43)
Input filter
Checkbox deactivated
(25 Hz)
activated
Explanation
The fieldbus coupler/controller signals
a diagnosis when at least one channel
of the I/O module reports the event:
•
Measurement range overflow
•
Measurement range underflow
•
Short circuit
•
Line break
Diagnostics reported by the I/O module
do not lead to the signaling of a
diagnosis by the fieldbus coupler.
Diagnostics reported by the I/O module
lead to the signaling of a diagnosis by
the fieldbus coupler.
*)
*)
*)
*)