Display Elements; Figure 5: Display Elements - WAGO 750-486/040-000 Manual

4ai 0/4-20ma ne43 ex i xtr 4-channel analog input; 0/4...20 ma; ne43; intrinsically safe; extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-486/040-000 4AI 0/4-20mA NE43 Ex i XTR
3.3

Display Elements

Figure 5: Display Elements

Table 7: Legend for Figure "Display Elements"
Channel Designation LED State Function
1
2
3
Status AI 1
A
Green
Error AI 1
B
Red
Status AI 2
C
Green
Error AI 2
D
Red
Status AI 3
E
Green
Error AI 3
F
Red
Not ready for operation or no or disturbed
Off
local bus communication, channel
deactivated
Ready for operation and undisturbed local
bus communication
Normal operation and/or diagnostics
Off
deactivated, or channel deactivated
Permissible measurement range
overrange/underrange, short circuit,
general error, wire break (for sensor types
"4 mA ... 20 mA" and "3.6... 21 mA")
Not ready for operation or no or disturbed
Off
local bus communication, channel
deactivated
Ready for operation and undisturbed local
bus communication
Normal operation and/or diagnostics
Off
deactivated, or channel deactivated
Permissible measurement range
overrange/underrange, short circuit,
general error, wire break (for sensor types
"4 mA ... 20 mA" and "3.6... 21 mA")
Not ready for operation or no or disturbed
Off
local bus communication, channel
deactivated
Ready for operation and undisturbed local
bus communication
Normal operation and/or diagnostics
Off
deactivated, or channel deactivated
Permissible measurement range
overrange/underrange, short circuit,
general error, wire break (for sensor types
"4 mA ... 20 mA" and "3.6... 21 mA")
Device Description
Manual
Version 1.0.0
21