Process Image; I/O Modules With Pt Resistance Sensors; Pt100; Table 16: I/O Modules With Pt Resistance Sensors - WAGO 750-461 Series Manual

2ai pt100/rtd, 2-channel analog input for resistance sensors for wago-i/o-system 750
Hide thumbs Also See for 750-461 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
Pos: 23 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 1/Prozessabbild - Überschrift 1 @ 4\mod_1240983067828_21.docx @ 31942 @ 1 @ 1
4

Process Image

Pos: 24.1 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Lokalbus/AI/Prozessabbild 750-0461 Einleitung @ 16\mod_1378299772322_21.docx @ 130789 @ @ 1
The I/O module transfers 16 bits per channel of measured data and, optionally, 8
status bits to the fieldbus coupler/controller. Access to the status bits depends on
the specific fieldbus system.
Pos: 24.2 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Lokalbus/Hinweis: Prozessabbildmapping abhängig von FBK/PFC, mit Status-/Controllbyte @ 4\mod_1242621308640_21.docx @ 33290 @ @ 1
Mapping of process data in the process image of fieldbus systems
The representation of the I/O modules' process data in the process image
depends on the fieldbus coupler/controller used. Please take this information as
well as the particular design of the respective control/status bytes from the
section "Fieldbus Specific Design of the Process Data" included in the description
concerning the process image of the fieldbus coupler/controller used.
Pos: 24.3 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Lokalbus/AI/Prozessabbild 750-0461 nach Varianten @ 5\mod_1251438991781_21.docx @ 41034 @ 23332333233 @ 1
4.1

I/O Modules with Pt Resistance Sensors

Table 16: I/O Modules with Pt Resistance Sensors

750-461
750-461/000-003
750-461/000-006
750-461/000-200
750-461/025-000
4.1.1

Pt100

The I/O modules 750-461and the versions 750-461/000-006 and 750-461/025-
000 calculate the resistance values of Pt100 sensors and output the data as
temperature values. The temperature values are displayed at a resolution of 1
digit per 0.1 °C in one word (16-bit). Temperature values below 0 °C are
represented in two's complement binary. As a result, 0 °C corresponds to the
numeric value 0x0000 and 100 °C to the numeric value 0x03E8 (dec. 1000). The
possible numeric range corresponds to the defined temperature range of −200 °C
to +850 °C for Pt100 sensors.
Evaluation Pt100
Measuring range: −200 °C to +850 °C
Evaluation Pt1000
Measuring range: −200 °C to +850 °C
Evaluation Pt100, optimized temperature drift
(0.001 %/K, conversion time 960 ms)
Measuring range: −200 °C to +850 °C
Evaluation Pt100, with status information for
S5-FB250 in the data word
Measuring range: −200 °C to +850 °C
Evaluation Pt100, extended temperature range
Measuring range: −200 °C to +850 °C
Process Image
27