WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
Pos: 26 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 1/Montieren - Überschrift 1 @ 3\mod_1225446744750_21.docx @ 24900 @ 1 @ 1
5

Mounting

Pos: 27.1 /Serie 750 (WAGO-I/O-SYSTEM)/Montieren/Demontieren/Montagereihenfolge @ 3\mod_1231770210031_21.docx @ 25992 @ 2 @ 1
5.1

Mounting Sequence

Fieldbus couplers, controllers and I/O modules of the WAGO-I/O-SYSTEM 750
are snapped directly on a carrier rail in accordance with the European standard
EN 60175 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler or controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Pos: 27.2 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Vorsicht/Vorsicht: Verletzungsgefahr durch scharfkantige Messerkontakte! @ 6\mod_1256193279401_21.docx @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
Pos: 27.3 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Achtung/Achtung: I/O-Module nur in vorgesehener Reihenfolge stecken! @ 6\mod_1256194177073_21.docx @ 43429 @ @ 1
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the
top. This mechanical coding helps to avoid configuration errors, which may
destroy the I/O modules. Therefore, insert I/O modules only from the right and
from the top.
Pos: 27.4 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Hinweis/Hinweis: Busabschluss nicht vergessen! @ 6\mod_1256194225557_21.docx @ 43432 @ @ 1
Don't forget the bus end module!
Always plug a bus end module (750-600) onto the end of the fieldbus node! You
must always use a bus end module at all fieldbus nodes with WAGO-I/O-
SYSTEM 750 fieldbus couplers or controllers to guarantee proper data transfer.