Climatic Environmental Conditions; Connection Type; Table 13: Technical Data - Climatic Environmental Conditions; Table 14: Technical Data - Field Wiring - WAGO 750-461 Series Manual

2ai pt100/rtd, 2-channel analog input for resistance sensors for wago-i/o-system 750
Hide thumbs Also See for 750-461 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
3.6.5

Climatic Environmental Conditions

Table 13: Technical Data – Climatic Environmental Conditions
Surrounding air temperature
(operation)
Surrounding air temperature
(operation) for components with
extended temperature range
(750-xxx/025-xxx)
Surrounding air temperature (storage) −25 °C ... +85 °C
Surrounding air temperature (storage)
for components with extended
temperature range (750-xxx/025-xxx)
Operating altitude
Relative humidity
Pollution degree
Protection type
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Pos: 21.28.1 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 3/Anschlusstechnik - Überschrift 3 @ 17\mod_1380123271324_21.docx @ 132788 @ 3 @ 1
3.6.6

Connection Type

Pos: 21.28.2 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung (alte Struktur)/Technische Daten/Anschlusstechnik/Technische Daten Verdrahtungsebene CC - 0,08 bis 2,5mm2 @ 17\mod_1380121238809_21.docx @ 132780 @ @ 1
Table 14: Technical Data – Field Wiring
Wire connection
Cross section
Stripped lengths
Pos: 21.28.3 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung (alte Struktur)/Technische Daten/Anschlusstechnik/Technische Daten Datenkontakte @ 17\mod_1380123495844_21.docx @ 132794 @ @ 1
Table 15: Technical Data – Data Contacts
Data contacts
Pos: 21.29 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Device Description
0 °C ... 55 °C
−20 °C ... +60 °C
−40 °C ... +85 °C
without temperature derating:
0 ... 2000 m;
with temperature derating:
2000 ... 5000 m (0.5 K/100 m);
max.: 5000 m
Max. 5 % ... 95 % without condensation
2
IP20
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
®
CAGE CLAMP
0.08 mm² ... 2.5 mm², AWG 28 ... 14
8 mm ... 9 mm / 0.33 in
Slide contact, hard gold plated, self-
cleaning