Figure 20: Text Detail - Marking Example For Approved Ex I I/O Modules; Table 38: Description Of Marking Example For Approved Ex I I/O Modules - WAGO 750-461 Series Manual

2ai pt100/rtd, 2-channel analog input for resistance sensors for wago-i/o-system 750
Hide thumbs Also See for 750-461 Series:
Table of Contents

Advertisement

50
Use in Hazardous Environments
Pos: 36.16 /Serie 750 (WAGO-I/O-SYSTEM)/Einsatz in Ex-Bereichen/Beispielbedruckung und Textdetail CEC_2017 @ 29\mod_1497865583297_21.docx @ 424736 @ @ 1
Figure 20: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 38: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Dust
Ex
nA
[ia IIIC]
IIC
T4
Gc
X
Gases
Ex
nA
[ia Ga]
IIC
T4
Gc
X
Pos: 36.17 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.4.1
Description
Explosion protection mark
Type of protection
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
Group
Temperature class
Equipment protection level (EPL)
Symbol used to denote specific conditions of use
Explosion protection mark
Type of protection
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
Group
Temperature class
Equipment protection level (EPL)
Symbol used to denote specific conditions of use
WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD

Advertisement

Chapters

Table of Contents
loading

Table of Contents