Ni1000 Tk6180; Table 22: Process Image, Ni1000 Tk6180, With Wire Break Diagnostics - WAGO 750-461 Series Manual

2ai pt100/rtd, 2-channel analog input for resistance sensors for wago-i/o-system 750
Hide thumbs Also See for 750-461 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
4.2.2

Ni1000 TK6180

The 750-461/000-005 version calculates the resistance values of Ni1000-TK6180
sensors and outputs the data as temperature values. The temperature values are
displayed at a resolution of 1 digit per 0.1 °C in one word (16-bit). Temperature
values below 0 °C are represented in two's complement binary. As a result, 0 °C
corresponds to the numeric value 0x0000 and 100 °C to the numeric value
0x03E8 (dec. 1000). The possible numeric range corresponds to the defined
temperature range of −60 °C to +250 °C for type Ni1000 TK6180 sensors.

Table 22: Process Image, Ni1000 TK6180, with Wire Break Diagnostics

Temperature
°C
< −60.0
−60.0
−50.0
0.0
50.0
100.0
150.0
200.0
250.0
> 250.0
Wire break at RL
1)
Process values below 0 °C are represented in two's complement binary.
2)
For version 750-461/003-000, the hex. value is 0x8001, dec. value -32767
3)
For version 750-461/003-000, the hex. value is 0x2134, dec. value 8500
The measured value can exceed a decimal range of −600 to +2500 before
limitation takes effect.
For the adjustable version 750-461/003-000, the process image is identical
except for the hex./dec. values in the overflow and underflow.
Resistance
Ω
Binary
< 691.60
'1000.0000.0000.0001'
691.60
'1111.1101.1010.1000'
742.60
'1111.1110.0000.1100'
1000.00
'0000.0000.0000.0000'
1291.00
'0000.0001.1111.0100'
1617.96
'0000.0011.1110.1000'
1986.20
'0000.0101.1101.1100'
2406.40
'0000.0111.1101.0000'
2891.31
'0000.1001.1100.0100'
> 2891.31
'0010.0001.0011.0100'
'0010.0001.0011.0100'
1)
Numeric value
Hex.
2)
0xFDA8
0xFDA8
0xFE0C
0x0000
0x01F4
0x03E8
0x05DC
0x07D0
0x09C4
3)
0x09C4
3)
0x09C4
Process Image
31
Status
LED
Byte
Error
Hex.
AI 1, 2
Dec.
2)
−600
0x41
ON
−600
0x00
OFF
−500
0x00
OFF
0
0x00
OFF
500
0x00
OFF
1000
0x00
OFF
1500
0x00
OFF
2000
0x00
OFF
2500
0x00
OFF
3)
2500
0x42
ON
3)
2500
0x42
ON
Manual