Electrical Connections - Single And Three Phase - Champion DH6000T-VHR Installation Manual

Table of Contents

Advertisement

Installation
Electrical Connection - Single and Three Phase
1.
Remove the right and front panels and position the machine near the final location.
2.
Route conduit to the mounting bracket located at the right rear corner of the machine
(see Fig. 9). Be sure to leave a 6 foot / 2 meter service loop to the machine.
3.
Remove the right and front panel to access the main terminal blocks. The machine may
have a one or two point electrical connection.
4.
Follow the Machine Electrical Connection Data Plates for the terminal block connections.
The data plates are glued in front of the blocks (Fig. 11).
FRONT VIEW
TERMINAL
BLOCKS
8
WARNING:
Electrocution may occur when working on energized circuits.
Disconnect power at the main breaker or service disconnect switch,
then lock out and tag it to indicate that work is being performed
on the circuit.
2-Point Booster Connection Data Plate
Mod: DH6000T
For supply connection, use copper connectors in accordance
with local electrical code. Rated Minimum 90°C (194°F).
Overcurrent Protection Device: Time Delay or Inverse Time
Circuit Breaker
Minium Supply Conductor Ampacity
Maximum Supply Overcurrent
Protection Device
Volt: 208-240
Series: VHR
50/50
50/50
Ph: 3
Hz: 60
Amp: 39-34
Fig. 11
Fig. 9
Fig. 10
AMPS
AMPS