Global Settings for Field Supply

9.5

Automatic Storage of System Parameters

9.6

Firmware Update

Parameter
Description
Diagnostics
The channel-related diagnostics can be enabled/disabled here
(for more information, see
module" on page
- lock
- unlock
Substitute value
The substitute value strategy outputs the substitute value or
strategy
the last valid output value, e.g in case a field bus is interrupted.
The following options are available:
- Activate the substitute value
- Retain last value
Substitute value
Enter here the process value that is released in case of an
error or if a field bus is missing. In the case of an error (e.g.
field bus interruption), this value is used with the "Switch to
Substitute Value" substitute value strategy.
- 0
- 1
Delivery status
The last value is a value that is reported at the contact before
the interference occurs. For example, this value can be a proc‐
ess value
Tab. 9-3:
Overview of adjustable parameters for the digital outputs
If a short circuit has occurred, the field supply is switched off 1000 ms. Then
the field supply is switched on again. If the short circuit condition remains, the
procedure is repeated.
Some field bus couplers provide the "System Parameter Handling" feature.
This function is used to identify changes to the configuration of the
IndraControl S67 node and to the automatic parameterization of the modules.
If a module is to be replaced due to a defect, the new module is not to be
reconfigured anymore. The stored parameters are automatically transferred
to the replaced module.
During a firmware update of the S67-DO8-HS-M12 module, the stored mod‐
ule parameters can be overwritten. Thus, check the parameterization after a
firmware update.
The firmware update can be carried out only by the Bosch
Rexroth Service.