Bosch Rexroth IndraControl S67 Application Description page 48

Digital module high speed 8 outputs
Hide thumbs Also See for Rexroth IndraControl S67:
Table of Contents

Advertisement

46/61
Bosch Rexroth AG
Diagnostics via LED Signals
Position
LED
Color/status
15
SB
Off
Red, flashing,
4 Hz
Red, flashing,
1 or 2 Hz
Green
Green and orange,
flashing,
1 Hz
Orange, flashing,
2 Hz
Orange and green,
flashing,
4 Hz
Orange, flashing,
1 Hz
Orange and green,
flashing,
2 Hz
Orange
Orange, flashing,
4 Hz
15
SB
Green, flashing,
1 Hz
Green, flashing,
2 Hz
Rexroth IndraControl S67 Digital Module High Speed 8 Outputs – 0.1 A (4×M12)
Cause
Low voltage
U
is not present
LS
S-BUS error at the module
The module is being restarted via
the field bus coupler
Data exchange is executed; proc‐
ess data values are valid. The mod‐
ule is in RUN status
The set substitute value is applied
to the module
The module has detected the S-
BUS
Detection of the last module in
IndraControl S67 node is executed
The field bus coupler addresses the
module in the IndraControl S67
node
S-BUS parameters are taken over
by the field bus coupler
The firmware is being updated
The module tries to establish a
communication with the field bus
coupler
The module is in HOLD state
The module is in STOP state
Tab. 10-1:
Operational message 1
DOK-CONTRL-S67DO8M12HS-AP02-EN-P
Remedy/Information
Check the supply voltage
Check whether the S-BUS cable is
connected. Check the S-BUS cable
for damages.
Check whether the firmware of the
field bus coupler is compatible with
the firmware of the module
If the flashing frequency is 1 Hz,
please contact the Bosch Rexroth
service
Can be set by the field bus coupler
if field bus is missing.
Check the field bus connection as
well as the status of the higher-lev‐
el controller
Check the S-BUS terminator and/or
the S-BUS wiring
All IndraControl S67 components
are being updated by the field bus
coupler within the node
Check the supply voltage of the up‐
stream IndraControl S67 compo‐
nent and/or check the S-BUS cable
for damages
Is initiated by the field bus coupler.
The last values output at the mod‐
ules are retained
Is initiated by the field bus coupler.
"0" is returned as output value