Process Images; General Information; Output Data - Bosch Rexroth IndraControl S67 Application Description

Digital module high speed 8 outputs
Hide thumbs Also See for Rexroth IndraControl S67:
Table of Contents

Advertisement

DOK-CONTRL-S67DO8M12HS-AP02-EN-P
Rexroth IndraControl S67 Digital Module High Speed 8 Outputs – 0.1 A (4×M12)
8

Process Images

8.1

General Information

8.2

Output Data

The process images of the module contained in the following chapters de‐
scribe the data position on the S-BUS. The field bus coupler application man‐
ual describes the conversion of the S-BUS process images to the respective
field bus process images.
The process image is divided into two areas: An area for output data and an
area for input data. The process image can contain process data with or with‐
out diagnostic information, depending on whether the transmission of the
synchronous
1)
diagnostic information has been activated. The diagnostic in‐
formation can only be activated by means of a field bus coupler as the cou‐
pler supports the function of the synchronous diagnostic (e.g. S67-PB-BK-
DI8-M8). Detailed information about activating the transmission of diagnostic
information is contained in the application manual of the field bus coupler in
the device description file chapter.
Synchronous diagnostics is disabled in the module in its delivery
status.
Detailed information can be found starting in
page
41.
Diagnosis:"overtemperature"
The "overtemperature" diagnosis of the outputs is only possible
when the output is switched on.
The process image for the process data that is sent from the field bus coupler
to the S67-DO8-HS-M12 module has a size of 1 byte. If a synchronous diag‐
nostic confirmation is parameterized for the module, the process image size
is 3 byte.
The process data and the diagnostic confirmation are structured as follows:
Synchronous diagnostic information specifies the cyclic diagnostic information
1)
transfer in the process image. By default, the cyclic diagnostic information transfer
in the process image is disabled in the module.
Bosch Rexroth AG
Process Images
chapter 9 "Parameterization" on
39/61

Advertisement