28/61
Bosch Rexroth AG
Mounting the Module
5.8

Mounting the Spacer in Case of Compact Arrangement

Rexroth IndraControl S67 Digital Module High Speed 8 Outputs – 0.1 A (4×M12)
By using the spacer, a sufficient mounting distance can be achieved when di‐
rectly mounting the IndraControl S67 components, and gaps can be elimina‐
ted where otherwise dirt and other substances could accumulate. In addition,
it is possible to optimize the cable routing of the actuators. For this purpose,
two fastening lugs each are included on the spacer for cable ties.
1. Disconnect the power supply from those devices on which you wish to
mount the S67-DO8-HS-M12 module.
2. To prevent the IndraControl S67 components from falling out when it is
mounted overhead, the spacer can only be moved in the designated
openings of the S67-DO8-HS-M12 module from below. To bind both
components, place the S67-DO8-HS-M12 module on the spacer for this
reason or push the spacer from the bottom into the S67-DO8-HS-M12
module.
3. Fasten the attached components on a flat surface by fastening the S67-
DO8-HS-M12 module to the grounded border of your system or to an‐
other grounding point with two M4 screws via the mounting holes.
Fig. 5-6:
Attaching a spacer on a module
4. When attaching further IndraControl S67 components, only one
IndraControl S67 component connected with a spacer can be attached
and screwed to the preceding component due to the mounting direction.
The last IndraControl S67 component is fastened without a spacer.
DOK-CONTRL-S67DO8M12HS-AP02-EN-P
DO8-HS
SB
F
6
X
4
4
X
7
3
2
5
X
2
0
X
3
1
1
24V
U
U
LS
A